ZENITH-S
MP37634
ZP90993-1
34
1.8 CERTIFICATES
Atex Components Certificate
IMQ 19 ATEX 033 U
IECEx Components Certificate
IECEx IMQ 19.0004 U
1.9 ENCLOSURE’S DEGREE OF PROTECTION
IP66
1.10 SERVICE TEMPERATURE RANGE
-50°C to +100°C
2. INSTALLATION
Suitably trained personnel in accordance with the applicable code of practice (e.g. IEC / EN 60079-14) and
the provisions of the national safety and accident prevention regulations and this instruction manual shall
carry out installation.
2.1 DOOR REMOVING
In order to make easy installation is possible to remove the door, following this steps:
1. Check the Tightened HINGE-NUT (2.5 Nm)
2. Remove the Seeger
3. Slip-off the pivot
4. Repeat the operation 1 and 2 for the other hinges
After the installation is done reassemble the door following the above steps reversing the order steps.
PIVOT
HINGE
SEEGER
SILICON GASKET
NUT
2.2 SAFETY INSTRUCTIONS
The IP rating of the enclosure shall be maintained for the area of installation by the use of correct arrangement of cable-gland,
blanking plug elements, adapters in accordance with the installation rules. Where other certified components are part of the
assembly, the user must take account of any limitation listed on relevant certificates.
The holes must be cut inside the approved drilling areas for each wall, and must be done with absolute quality and without burrs.
The cable glands are usually fitted during installation.
The enclosure must be installed in absence of damage and free of defects.
2.3 ACCESSORIES
The installation of the accessories must be performed before the installation of the enclosure, and following the relevant instruction
sheets. Only approved and genuine SCAME accessories must be used.