background image

 

BSK-EN fire damper 

 

INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS 

 

Tender text 

 

Construction subject to change 

 

No return possible 

Version: 2018-11-14 | Page 15 

SPECIFICATION TEXT 

BSK-EN  is  tested  according  to  EN  1366-2  in  connection  with 
Declaration  of  performance  (DoP)  no.  01-01-  DoP-  BSK-EN-
2014-10-29.  
It has the certificate of consistency of performance according 
to EU-BauPVO 1035-CPR-ES054987. The category according to 
EN 13501-3 is EI 120 (v

e

, h

o

 i↔o) S. 

 

 

Housing  made  of  galvanised  sheet  steel,  cold  and  hot 
leakage requirements according to EN 1366-2 are met u-
sing  circumferential  PUR  sealings  and  intumescent  seals.  
Optionally (at an extra charge) with DD coating (two-com-
ponent paint, PU-based), inside/outside. 

 

Moulded connecting flanges with centre hole, corner angle 
with long hole for simple channel mounting and high sta-
bility. 

 

Shut-off damper made of fibre-silicate board. 

 
For  connection  to  ventilation  ducts  (one-  or  two-sided),  air 
flow direction optional. 

 

Installation: 

 

with horizontal damper leaf axle 

 

in solid walls and solid ceilings 

 

Product: SCHAKO 

type BSK-EN

 

CE marking: 1035-CPR-ES054987

 

 

Dimensions: 
Width (B):  .................... mm 
Height (H):  .................... mm 
Length (L):  500 mm 
Model: right / left 
 
(Unless specified otherwise in the order details, the mechani-
cal  model  "Right"  and  fusible  link  with  trigger  temperature 
72°C is supplied). 

 

Alternative models or accessories (at an extra charge)

 

("select as required"). 

 

Housing  with  DD  coating  (solvent-based  two-component 
paint, PU-based - RAL 7035 / light grey). 

 

Electric limit switch type ES for position indicators "OPEN" 
or/and "CLOSED", switching element with an NC and NO 
contact respectively: 

 

Type ES 1 Z  : "CLOSED" 

 

Type ES 1 A  : "OPEN" 

 

Type ES 2: "OPEN" and "CLOSED" 

 

Electric spring return actuator with thermoelectric release 
device BAT or BAE72B-S. 

 

Releases at a duct inside temperature of 72°C (opti-
onally: 95°C and 120°C) containing integrated micro 
switches for indication of damper end positions (24 
V drive with connector). 

 

Type 

B10 (BFL24-T-ST SO) 

 

 

B11 (BFL130-T SO) 

 

 

B20 (BFN24-T-ST SO) 

 

 

B21 (BFN230-T SO) 

 

 

B30 (BF24-T-ST SO) 

 

 

B31 (BF230-T SO) 

 

 

Electrical  spring  return  drive  with  thermoelectric  release 
device BAE72TL 

 

Releases at a duct inside temperature of 72°C (opti-
onally:  95°C)  containing  integrated  micro  switches 
for  indication  of  damper  end  positions,  connection 
to LON or Belimo MP bus systems possible via com-
munication devices. Available for all dimensions. 

 

Type B40 (BF24TL-T-ST SO; 24V AC/DC) 

 

Communication  device  BKN230-24LON  for  connec-
tion to LON bus system 

 

Communication  device  BKN230-24MP  for  connec-
tion to Belimo MP bus system 

 

 

Summary of Contents for BSK-EN

Page 1: ...dimensions 3 Mounting information 5 Installation information 6 Technical data 7 Accessories 9 Legend 14 Specification text 15 Identification label 17 Maintenance or functional test 18 Certificate of...

Page 2: ...be connected both on non combustible and com bustible ventilation ducts MODELS Housing made of galvanised sheet steel cold and hot leakage requirements according to EN 1366 2 are met u sing circumfer...

Page 3: ...50 650 700 700 750 750 800 800 900 1000 1100 1200 1300 1400 1500 Table 1 Available sizes Housing length L 500 mm All width and height dimensions can be combined Release device always on H side On requ...

Page 4: ...cting piece RS Pipe connecting piece a 50 mm Minimum distance between the front edge of the open damper leaf and the fi nishing protective grating ASG flexible connecting piece FS or pipe connecting p...

Page 5: ...otection mortar of the cor responding grade The minimum gap size smin is 50 mm If the fire damper is installed during the construction of the ceiling the gaps s can be omitted The mortar bed depth has...

Page 6: ...hey must be created in the direct vicinity in the connected ventilation ducts Inspection o penings are not available therefore they must be created in the direct vicinity in the connected ventilation...

Page 7: ...LWA dB A KF1 LWA2 dB A LWA1 dB A x KF2 LWA Abst1 dB A LWA1 dB A KF3 LWA1 Abst2 dB A LWA2 dB A KF3 p1 p x KF4 p2 p1 x KF5 200 3 1 05 7 2 15 1 66 250 3 1 07 7 1 8 1 69 300 2 1 09 7 1 55 1 72 350 2 1 10...

Page 8: ...3 40 1 41 8 45 4 49 0 52 5 56 1 59 6 63 2 66 7 Table 4 Weight table kg FREE CROSS SECTION Free cross section m2 Width mm 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 140...

Page 9: ...VT 1 Pipe connecting piece type RS 1 1 Standard model galvanised sheet steel powder coated RAL 9010 pure white and DD coating RAL 7035 light grey possible LIMIT SWITCH TYPE ES Electric limit switch fo...

Page 10: ...sition is possible in the de energised state It is unlocked manually On site function control is possible by means of the control key of BAT or BAE72B S Spare parts Temperature fuse for temperature in...

Page 11: ...dimensions BSK EN with B10 B11 approx 102 mm BSK EN with B20 B21 approx 106 mm BSK EN with B30 B31 approx 120 mm Figure 12 Damper dimensions 200 225 250 275 300 325 350 375 400 450 500 550 600 650 700...

Page 12: ...IEC EN II protective insulation Degree of protection IEC EN IP54 Ambient temperature Normal operation 30 55 C 30 50 C Storage temperature 40 55 C 40 50 C Ambient humidity 95 r H non condensing Table...

Page 13: ...ard flammable according to EN 13501 1 with welded lip seals sealing degree C according to EN 13180 EN 1507 temperature resistant from 20 to 80 C Flexible part of the connecting piece polyester fabric...

Page 14: ...he flow generated noise adjusted for diffe rent values of B mm in the model with finishing protective grating ASG KF2 dB A A weighted sound power level of the flow generated noise adjusted for diffe r...

Page 15: ...eft Unless specified otherwise in the order details the mechani cal model Right and fusible link with trigger temperature 72 C is supplied Alternative models or accessories at an extra charge select a...

Page 16: ...80 C Flexible part of the connecting piece polyester fabric must have a length lmin of 100 mm when mounted this gives an installation dimension of approx L 160 mm The required equipotential bonding mu...

Page 17: ...to change No return possible Version 2018 11 14 Page 17 IDENTIFICATION LABEL 1035 13 SCHAKO Iberia S L Pol Ind R o G llego Calle B nave 3 E 50840 San Mateo de G llego Zaragoza 14 ESPA A 01 01 DoP BSK...

Page 18: ...h into the swivelling range of the damper leaf and hand lever There is a risk of injury The fire damper must close automatically 1 1 3 Test of the snap in locking device Pull the disc pos 1 at the han...

Page 19: ...r Press switch pos 1 on the thermoelectric trigger device pos 2 thus the spring return actuator is disconnected from the power supply pos 3 alternatively interrupt on site power supply Fire damper mus...

Page 20: ...______________ The following function steps have been carried out according to the documents Installation mounting and operating instruc tions before commissioning Next functional check in ___________...

Page 21: ...4 Page 21 Functional test protocol for fire dampers Cons no ____________________ Defects found during the test on _____________________ Sluggishness due to soiling Any remaining mortar must be removed...