SERVICE 

 

FUNCTIONAL TEST, MAINTENANCE/CLEANING, REPAIR 

 
Impure and humid air may impair permanent operational sa-
fety. This is the reason why the function of all fire dampers 
must be checked every six months after commissioning of 
the ventilation system. If two consecutive functional tests 
show no defects, the fire dampers only have to be tested at 
a yearly interval. If maintenance agreements are made for 
ventilation installations, it is recommended to include the 
functional tests of the fire damper in these maintenance ag-
reements. 
 

1. Manual trigger device 

1.1. Visual inspection 

 

Check the fire damper for damage and contamina-
tion (e.g. housing, damper blade, seals). 

 

Perform necessary cleaning. 

 

1.2 Manual triggering – Closing the fire damper 

 

Pull manual unlocking disc (pos. 1) at the hand le-
ver (pos. 2), this removes the locking (in the open 
position) of the locking bolt (pos. 4) in the trigger 
device (pos. 3). 

 

Hand lever has been released and is moved toward 
the closed position by spring force. 

ATTENTION! Do not reach into the pivoting range of the 
damper blade and of the manual lever. There is a risk of in-
jury. 

 

The fire damper must close and lock automatically 
(locking of the damper blade in the closed positi-
on). 

 

1.3 Opening the fire damper 

 

Pull manual unlocking disc (pos. 1) at the hand le-
ver (pos. 2) and move it toward the trigger device 
(pos. 3) 

 

Locking bolt (pos. 4) must snap into the trigger de-
vice (pos. 3) 

 

The fire damper is ready for operation again (dam-
per blade is locked in the open position). 

 
 

S = Lubricate moving parts (bearing) only if they are not run-
ning smoothly (lubricant: free of resin and acid). 
 

 
 
 

 

 

1.4 Replacing the fusible link (if necessary) 

 

If the fusible link is damaged or corroded, for example, it 
is necessary to replace it. 

 

Perform manual triggering as described in section 1.2. 

 

Unscrew the fastening screws (2 pieces, pos.5), pull the 
release device out by turning it 90° and remove it from 
the housing. 

 

Compress the retainer screws of the fusible link holder 
(pos. 7) using a suitable tool (e.g. pliers) and replace the 
fusible link by a replacement fusible link (pos. 6). 

 

Insert the release device and fasten it with screws (make 
sure that the position of the coding screw with regard to 
the coding hole is correct). 

 

Finally a functional test has to be made. 

 

BSK-RPR-EU with manual trigger 

 

 

Figure 20: Side view BSK-RPR-EU (manual trigger) 

 

Figure 21: Front view BSK-RPR-EU (manual trigger) 

 

 

Figure 22: Trigger device BSK-RPR-EU 

Summary of Contents for BSK-RPR-EU Series

Page 1: ...ances or p data es ch urn actuators rts on texts ranch offices ures tables di chad KG 10 drive s n projecting end agrams ds 1 1 1 1 1 1 2 2 Te Fa ww 1 3 6 7 7 8 10 10 11 13 15 17 21 23 Install elephon...

Page 2: ...tumescent seals Horizontal position of the damper blade axle The installation position is independent of the air flow direction Thermal trigger via fusible link 72 C optionally at an extra charge with...

Page 3: ...urn possible Version 2015 02 01 Document 09 48 Page 3 MODELS AND DIMENSIONS BSK RPR EU S plug in connection Figure 1 Dimensions BSK RPR EU S BSK RPR EU F flanged connection Figure 2 Dimensions BSK RPR...

Page 4: ...PR EU S is delivered by default with a rubber lip seal Figure 3 Rubber lip seal Trigger device thermomechanical Figure 4 Trigger device BSK RPR EU Flange bores BSK RPR EU F Figure 5 Flange bores Table...

Page 5: ...de and the finishing protective grating ASG RF RS Use The fire damper type BSK RPR EU can be installed as shown in the following table Table 4 Usability BSK RPR EU F Figure 7 Damper blade projecting e...

Page 6: ...e dampers before and after mounting and ensure ready access Electrical installations or work on electrical components may only be carried out by skilled electricians The supp ly voltage must be switch...

Page 7: ...des with ventila tion ducts BK Fire damper BSK RPR EU ASG Finishing protective grating type ASG 1 VT Extension piece type VT LL Ventilation duct SW Shaft wall SR Closing direction LR Air flow directio...

Page 8: ...to 250 Nominal sizes 250 to 500 Diagram 1 Pressure loss and flow generated noise without finishing protective grating Application limits max operating pressure of 1000 Pa at vstirn 10 m s Pressure los...

Page 9: ...00 98 2 44 2 74 2 49 2 80 125 123 2 83 3 21 2 89 3 29 140 138 3 06 3 49 3 13 3 57 160 158 3 35 3 84 3 43 3 93 180 178 3 65 4 20 3 74 4 31 200 198 3 97 4 59 4 07 4 70 224 222 4 37 5 07 4 48 5 19 250 24...

Page 10: ...ignalling and switching bus system type EasyBus Fire damper mini controller BKSYS Extension piece type VT RF 1 Assembly part type REBT 2 required for installation of the smoke detection system type RM...

Page 11: ...upply voltage in accordance with regula tions and unlocked mechanically Display of the damper end positions is possible by me ans of integrated micro switches via potential free changeover contacts co...

Page 12: ...position W 0 8 1 1 Power consumption dimensioning 4 VA Imax 8 3 A 5 ms 6 5 VA Imax 4 A 5 ms Auxiliary switch 2 x EPU Switching capacity of auxiliary switch 1 mA 3 0 5 inductive A AC 250 V Connection...

Page 13: ...2 on page 4 Nominal size D mm L mm The dimension L depends on the nominal size 100 98 160 125 123 140 138 160 158 180 178 200 198 224 222 250 248 280 278 315 313 355 353 400 398 450 448 500 498 190 T...

Page 14: ...248 280 278 315 313 355 353 400 398 450 448 500 498 Table 10 Dimensions REBT Figure 18 Round duct assembly type REBT side view front view and top view Position indicator type MSZ Figure 19 Position in...

Page 15: ...1 V2A Housing with DD coating solvent containing two component top coat based on polyurethane var nish RAL 7035 light grey inside outside Housing with powder coating RAL 9010 pure white inside and out...

Page 16: ...charge for anticorrosive paint inside and outside DD coating two component top coat based on polyurethane varnish RAL 7035 light grey Extra charge for powder coating RAL 9010 pure white inside and out...

Page 17: ...e of the damper blade and of the manual lever There is a risk of in jury The fire damper must close and lock automatically locking of the damper blade in the closed positi on 1 3 Opening the fire damp...

Page 18: ...pply Fire damper must close automatically locking is performed by blocking the spring return actuator 2 3 Replacement of the thermoelectric release device if necessary Exchange takes place by unscrewi...

Page 19: ...no Series Release device The following function steps have been carried out according to the documents installation mounting and operating instructions Prior to com missioning Next functional test in...

Page 20: ...chako de Web www schako de Sample Functional test protocol for fire dampers Cons No ____________________ Defects found during the test on ________________________________________ Sluggishness due to s...

Page 21: ...02 51620946 Fax 385 51 701 470 info europersis gr insupco netvision net il info schako it ri intel trade hr www europersis gr www insupco com www schako it www intel trade hr Luxembourg Niederlande st...

Page 22: ...00 Praha 10 Zabehlice San ve Tic Ltd Sti Tel 421 337 741 843 Calle B nave 3 Tel 42 02 727 680 43 Pursaklar Sanayi Sitesi Fax 421 337 741 843 E 50840 San Mateo de G llego Fax 42 02 727 693 93 Karaca re...

Page 23: ...ng return actuator 11 Figure 15 Connecting diagram B10 B11 11 Figure 16 Extension piece type VT RF 13 Figure 17 Finishing protective grating type ASG RS RF 13 Figure 18 Round duct assembly type REBT s...

Reviews:

Related manuals for BSK-RPR-EU Series