Fire damper BSK-RPR-EU
Technical documentation
CE marking
Construction subject to change
No return possible
Version: 2021-07-01 | Page 18
Wire or punch grille with a mesh size of ≤ 20 mm
Intended use:
to be fitted for one-sided connection
Remember that the minimum distance to the open
damper leaf a
min
is 50 mm, if necessary, use extension
piece
Position indicator type MSZ
Figure 25: Position indicator type MSZ
38 Galvanised steel cable
39 Clamping nipple
40 Position indicator
41 False ceiling
Steel cable -galvanized- (pos. 38) with clamping nipple
(pos. 39) and position indicator (pos. 40); steel cable and
position indicator must be arranged perpendicularly.
Intended use:
Mechanical position indicator (article 3019870) for false
ceilings (pos. 41). Usable for each mechanically operated
BSK-RPR-EU with hand lever.
Legend
V
ZU
[m³/h] [l/s]
= Supply air volume
Δp
st
[Pa]
= Static pressure
L
WA
[dB(A)]
= A-weighted sound power level
v
stirn
[m/s]
= Face velocity
ρ
[kg/m³]
= Density
B
[mm]
= Width
H
[mm]
= Height
L
[mm]
= Length
min.
= at least
or
= or
ap-
prox.
= approximately
BS
= Operating side
NBS
= Non-operating side
OK
= OKAY
CE MARKING
12
0761
SCHAKO KG
Weidenäcker 9
D-88605 Meßkirch
2021
DoP-BSK-RPR-EU-2017-08-09
EN 15650:2010
Fire Damper
Type/version
BSK-RPR-EU
Nominal conditions of
activation / sensitivity:
- Load bearing capacity of the
temperature-sensitive measuring sensor
- Response temperature of the
temperature-sensitive measuring sensor
passed
Response delay
(Response time):
- Closing time
passed
Operational safety:
- Cyclic testing (50 cycles)
passed
Fire resistance:
- Cross-section maintained
- Integrity E
- Heat insulation I
- Smoke leakage S
- Mechanical strength (under E)
- Cross-section (under E)
EI 120
(v
e
i
↔
o) S
Durability of the
response delay:
- temperature-sensitive measuring sensor
Response temperature and load bearing capacity
Durability of the operational safety:
- Test of the opening and closing cycle
passed
passed