Fire damper BSK-RPR 

 

 

Additional operating instructions according to ATEX 2014/34/EU

 

 

Models and dimensions

 

Construction subject to change 

 

No return possible 

Version: 2020-09-01 | Page 9 

Limit switch type ES-Ex 

Limit switch for application in areas subject to explosion haz-
ards 
 

II 2G Ex d IIC T6/T5 Gb, 
 
II 2D Ex tb IIIC T 80°C/ 95°C Db 

IP65; 250V / 6A AC15; 230V / 0.25A DC13; -20°C ≤ Ta ≤ +65°C 

 

 

 

Figure 9: Circuit diagram limit switch type ES-Ex 

Damper positions that can be displayed: 
EXZ (type ES-Ex-Z: "CLOSED")  
EXA (type ES-Ex-A: "OPEN")  
EX2 (type ES-Ex-2: "OPEN" and "CLOSED") 

General information 

 

During mounting or installation, there is a risk of injuries. 
To avoid any possible injuries, personal protective equip-
ment (PPE) must be worn. 

 

Fire dampers must be installed such that external forces 
do not impair their permanent functioning.  

 

Ventilation  ducts  must  not  exert  significant  forces  on 
walls, supports or ceilings and thus also on fire dampers 
as a result of thermal expansion (in case of fire). 
Appropriate  compensation  measures,  such  as  the  ar-
rangement of flexible spigots (SCHAKO type FS) or a suit-
able  duct  routing  (duct  angles and  distortions), must  be 
taken as required. National regulations must be observed 
and implemented 

 

Prior  to  installing  the  fire  damper,  the  possible  connec-
tions of the ventilation ducts must be checked. Extension 
parts (on site or as accessories SCHAKO type VT) might be 
necessary,  e.g.  for  large  wall  and  ceiling  thicknesses. 
When  connecting  duct  components,  a  fastening  type 
must  be  selected  that  causes  no  damage  to  the  fire 
damper or its accessories. 

 

During mounting it may be required to provide reinforce-
ments for the housing or the like.  

 

The  requirement  of  statically  load-bearing  lintels  may 
have to be taken into consideration.  

 

If a fire damper is not filled with mortar on all four sides, 
installation and mounting aids on site must be removed.

 

 

Improper transport/handling may result in damage/func-
tional  impairment.  In  addition  to  that,  the  film  of  the 
transport packaging must be removed and the delivery in-
spected for completeness.

 

 

In  storage,  fire  dampers  must  be  protected  from  dust, 
dirt, moisture and the effects of temperature (e.g. direct 
sunlight, heat-emitting light source, etc.). They must not 
be exposed to direct effects of the weather and must not 
be stored below -20 °C or above 50 °C.

 

 

The fire damper must be protected from dirt and damage. 
After installation is complete, any dirt must be removed 
immediately.

 

 

Enough  space  must  be  provided  for  installation,  mortar 
lining, etc. 

 

 

Carry out a functional check of the fire damper before and 
after mounting and ensure ready access. 

 

 

Electrical  installations  or  work  on  electrical  components 
may only be carried out by skilled electricians. The supply 
voltage must be switched off when performing this work 
and secured against being switched on again. 

 

We would like to point out that only suitable cleaning ma-
terials may be used for cleaning fire dampers in stainless 
steel design! 

Summary of Contents for BSK-RPR

Page 1: ...RPR 2020 09 01 CLASSIFICATION AND STANDARDS Classification according to EN 13501 3 depending on the mounting situation EI 90 ve ho i o S Product standard EN 15650 Test standard EN 1366 2 PERFORMANCE D...

Page 2: ...Contents Construction subject to change No return possible Version 2020 09 01 Page 2 TABLE OF CONTENTS Table of Contents 2 General conditions 3 Description 4 Models and dimensions 5 Type plate 11 Ord...

Page 3: ...d DESIGNATED USE The devices have been designed for use in ventilation systems in areas subject to explosion hazards according to the ATEX marking Device group II Zones 1 2 and 21 22 These devices are...

Page 4: ...ilation system by means of ventilation ducts either on one or on both sides When connected on one side security grille made of non flammable building materials EN13501 1 must be provided on the opposi...

Page 5: ...amper blade 3 Hand lever 4 Locking profile 5 Release device 6 Fusible link 7 Mounting frame AR 8 Actuator unit 9 Earthing connection 10 Actuator ExMax 5 10 BF X14 X15 11 Safety temperature limiter Rub...

Page 6: ...le Version 2020 09 01 Page 6 BSK RPR S with mounting frame AR Figure 4 Dimensions of the BSK RPR S with mounting frame AR Figure 5 Dimensions of BSK RPR S with installation frame AR with actuator ExMa...

Page 7: ...5 58 13 40 7 03 14 85 280 278 6 31 16 55 7 79 18 03 7 17 17 41 8 65 18 89 315 313 7 14 18 40 8 62 19 88 8 13 19 39 9 61 20 87 355 353 8 08 20 53 9 56 22 01 9 19 21 64 10 67 23 12 400 398 9 09 22 89 1...

Page 8: ...ula tions Technical data actuator ExMax 5 10 BF X14 X15 Power supply 24 240 V AC DC 10 each self adaptable Frequency 50 60 Hz 20 Power consumption Holding max 20 W Heating capacity approx 16 W Current...

Page 9: ...t be necessary e g for large wall and ceiling thicknesses When connecting duct components a fastening type must be selected that causes no damage to the fire damper or its accessories During mounting...

Page 10: ...by contact or inhaling hazardous substances must be excluded by taking appropriate safety measures Prior to functional check or inspection all system components up and downstream of the device must be...

Page 11: ...damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Type plate Construction subject to change No return possible Version 2020 09 01 Page 11 TYPE PLATE Figure 10 BSK RPR type...

Page 12: ...02 MODEL S Plug in connection F Flanged connection 03 NOMINAL SIZE 100 125 140 160 180 200 224 250 280 315 355 400 450 500 in mm always three digits 04 LENGTH 580 or 455 S model 500 or 375 F model in...

Page 13: ...ess 120 mm metal post includes R04 I R22 Installation kit type GDL for wall thickness 125 mm metal post includes R04 I R23 Installation kit type GDL for wall thickness 140 mm metal post includes R04 I...

Page 14: ...amper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 14 CERTIFICATE OF CONFO...

Page 15: ...Fire damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 15...

Page 16: ...43 Luxembourg L 2343 Luxembourg A 1060 Wien PL 05 500 Piaseczno Phone 352 403 157 1 Phone 352 403 157 1 Phone 43 1 890 24 62 Phone 48 22 7263570 Fax 352 403 157 66 Fax 352 403 157 66 Fax 43 1 890 24 6...

Page 17: ...ilippendichtung 5 Abbildung 4 Abmessungen BSK RPR S mit Anbaurahmen AR 6 Abbildung 5 Abmessungen BSK RPR S mit Anbaurahmen AR mit Antrieb ExMax 5 10 BF X14 X15 6 Abbildung 6 Abmessungen BSK RPR F 6 Ab...

Reviews: