Installation, Mounting and Maintenance DISA-300
Z11/23 - 12
Construction subject to change.
No return possible!
Version:
Nozzle configuration C
Nozzle configuration D
Troubleshooting
Vzu (m
3
/h)
0 20 40 60 80 100
200
300
0
2
0
4
0
6
0
8
0
100
200
300
'
P (Pa.)
900-C
1200-C
1500-C
1800-C
2100-C
2400-C
2700-C
3000-C
Vzu (m
3
/h)
0 20 40 60 80 100
200
300
0
2
0
4
0
6
0
8
0
100
200
300
'
P (Pa.)
900-D
1200-D
1500-D
1800-D
2100-D
2400-D
2700-D
3000-D
Problem
Possible cause
Solution
The unit does not cool or heat suffi-
ciently
Air inlet and outlet of the inner unit clogged
Remove foreign material and clean the unit
Air in the interior of the register
Ventilation of the hydraulic system
Please inform the installer
Installed unfavourable or malfunctions at the temperature
control or sensor
Install thermostat in a different place
Clogging in the interior of the unit or at the air inlet
Remove foreign material and clean the inte-
rior of the unit
The unit is losing water
Condensate in the register
Modify the register water inlet temperature
The water circuit of the register is leaking
Please inform the installer
Register damaged
Incorrect valve or hydraulic connection
The unit is working with too much
noise
The air intake or air blow openings or the lines are clogged. Remove foreign material and clean the unit
Loose screws and fastening elements
Tighten screws
Foreign material or dirt on register surface
Remove foreign material by careful
brushing