Smoke extraction damper ERK-SO
TECHNICAL DOCUMENTATION
CE marking |
Construction subject to change
No
return
possible
Version:
2017-11-28
|
Page
38
Profile connection frame type PAR
, made of galvanised sheet
steel, for connecting flexible spigot type FS-E or security grille
ASG-E.
o
mounted ex works (recommended), on one side (operat-
ing side [BS] (PAR1) or wall side [MS] (PAR2)) or on both
sides (PAR3).
o
delivered loose: 1 piece (PAR4)
2 pieces (PAR5)
Product:
SCHAKO
type PAR
Dimensions:
Width (W): .................... mm
Height (H): ..................... mm
Mounting bracket type WE-S
, made of galvanised sheet steel,
dimensions 100 x 100 x 160 mm. Required for installation on
solid walls and in solid ceilings. The exact arrangement and
number of mounting brackets WE-S must be selected according
to the ERK-SO dimensions.
Product:
SCHAKO Mounting bracket type WE-S
Dimensions (W/H according to the damper dimension)
Width (B):
.................... mm
Height (H):
.................... mm
The mounting brackets WE-S (loose) are delivered only if they
have been explicitly ordered and according to specifications for
the mounting situation.
Ceiling frame type DR-S
, made of silicate structural panels, di-
mensions 100x40 mm. Required for vertical installation on solid
ceilings. Up to dimensions W and H = 500 mm, additional
mounting brackets made of steel (2 pieces) are required for
ERK-SO. The ceiling frame DR-S is pressed circumferentially
against ERK-SO and solid ceiling and screwed to the ceiling. If it
is necessary due to the size, the mounting brackets made of
steel must be additionally screwed to the ERK-SO housing and
ceiling with DR-S.
The connection between ERK-SO and solid ceiling must be ad-
justed beforehand using water glass glue (SBK 2000) or estab-
lished.
Product:
SCHAKO
Ceiling frame type DR-S
Dimensions (W/H according to the damper dimension)
Width (B):
.................... mm
Height (H):
.................... mm
The ceiling frame DR-S (loose) is delivered only if it has been ex-
plicitly ordered and according to specifications for the mount-
ing situation.
CE MARKING
Figure 29 - CE marking
16
0761
SCHAKO Klima-Luft
Ferdinand Schad KG
Werk SO / Weidenäcker 9
D-88605 Meßkirch
2016
DoP-ERK-SO-2016-07-01
EN 12101-8:2011
Smoke extraction damper
Multi compartment
Type/version
ERK-SO
Nominal conditions of
activation/response
sensitivity:
Opening/closing during the
the test at the right time
and within the allowed time period
MA -
passed
Response delay/
closing time:
MA -
passed
Operational safety:
10,000 switch
cycles -
passed
Fire resistance:
- Fire integrity - E
- Heat insulation - I
- Smoke tightness - S
- Mechanical
dimensional stability (under E)
- Maintaining the
cross-section (under E)
EI 90 (v
edw
,
h
ow
, i
↔
o) S
1000 C
10000
MA multi
Durability of:
- the response delay
- the operational safety
passed
passed