2

3. Storage

The ACN-ARN smoke fans can stand 
outdoor storage for 1 month provided 
the packing is intact. Fans with no or bro-
ken packing must be stored in sheltered 
locations.
If the fans are stored indoors under well-
ventilated conditions with no risk of con-
densation the storage period may be ex-
tended to 6 months. The storage place 
must not be exposed to vibrations likely 
to damage the motor bearings.
If the storage period exceeds 3 months, it 
is recommended to turn the rotor re-
gularly by hand.

4. Installation

4.1 Preparing for installation

Follow the directions below to ensure a 
safe work environment and fan function-
ality.

Checklist prior to installation

• The rotor must rotate freely in the 

casing and have equal blade tip 
distances to the casing around the 
circumference.

• For outdoor installations the fans 

must be sheltered. Fans, motors and 
frequency drives must be installed 
so they are not exposed to rain or 
dripping water. 

• Avoid static electricity by 

grounding the fan during 
installation. For instance by 
assembly on non-conducting 
vibration dampers and 
foundations.

4.2 Installation

Fans must always be installed so that the 
rotating parts cannot be touched. The fan 
must be provided with wire guards on 
the inlet and outlet sides. If ducts are con-

nected, they should be provided with 
wire guards on the inlet side.

The fan is provided with an arrow-plate 
denoting the direction of airflow 
through the fan casing. See during instal-
lation that the fan is oriented so as to pro-
vide the desired direction of airflow in 
the system.
The best way of installing the fan is with 
a support frame (optional accessory), but 
it may also be suspended in the fan cas-
ing flanges or in special carriers.
The carriers must not hamper the free in-
let and outlet of air.

Important:

The vibration level of the 
installation depends on 
how the fans are installed, 
the operational 
conditions and the 
natural frequency of the 
foundation and supports.
Follow the below 
guidelines to avoid 
resonance.

- Soft suspension:

 Fan is 

fixated through springs 
or dampers. The natural 
frequency (Hz) of the 
system should be at least 
20% below fan speed.
Soft suspensions are 
available from Novenco.

- Stiff suspension:

 Fan is 

fastened to a duct or a 
stiff wall through holes 
in the flanges. The 
natural frequency of this 
system should be at least 
20% above fan speed.

- Elastic structure:

 Fan is 

fastened to an elastic 
structure. The natural 
system frequency 
should be at least 20% 
higher or lower than fan 
speed.

The owner is responsible 

for compliance with the 
above requirements. Non-
compliance affects the 
product guarantee.

Figure 1. Mounting of wire guard
(optional accessory) in flanged outlet

20

Ø400 - Ø560:

Ø630 - Ø1000:

Ø1120 - Ø1600:

6 x Ø7 mm

8 x Ø7 mm

8 x Ø9 mm

Eyebolt

Nut

Figure 2. Assembly of horizontal support frame for ACN-ARN

Figure 3. ACN mounted on horizontal support frame with anti-vibration dampers

05

06

07

Summary of Contents for NOVENCO NovAx ACN SMOKE

Page 1: ...Pure competence in air 918149 0 ACN ARN SMOKE INSTALLATION AND MAINTENANCE ENGLISH ...

Page 2: ...pplied with approval num ber class or category are also mentioned as well as test standard applied EN 12101 3 Fan pressure air quantity out put and maximum speed per minute are also on the fan nameplates The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fans type ACN AR...

Page 3: ...n is provided with an arrow plate denoting the direction of airflow through the fan casing See during instal lation that the fan is oriented so as to pro vide the desired direction of airflow in the system The best way of installing the fan is with asupportframe optionalaccessory but it may also be suspended in the fan cas ing flanges or in special carriers The carriers must not hamper the free in...

Page 4: ...fig 6 The duct or inlet cone on the fan inlet side must be designed to ensure smooth and undisturbed airflow ACN ARN smokefansarepreparedforcircularduct connection on both inlet and outlet sides Flanges supplied as standard for type ACN ARN comply with Eurovent 1 2 Systems with higher vibration levels or more exacting performance require ments must be provided with expansion joints between fan and...

Page 5: ... 7 mm s RMS measured radially at 2 points 90º offset and at the free shaft end of the motor Otherwise the fan must be balanced Operation at vibration levels exceeding 11 mm s RMS is not allowed for fixed fan positions Operation at vibration levels exceeding 18 mm s RMS is not allowed for fans on support frames or anti vibration dampers ISO 2954 Requirements for instruments for measuring vibration ...

Page 6: ...an casing must be the same throughout the circumference If neces sary adjust the motor location in the sus pension arrangement Now mount centre screw item 01 cen tre disc item 02 and hub cover item 03 Replace lock washers or lock nuts during fan assembly Finally connect motor cable item 13 in terminal box item 12 and ducts if any To start the fan follow the procedure de scribed in section 5 Start ...

Page 7: ... A S AirBox and NovAx are trademarks of Novenco Building Industry A S Other trademarks appearing in this doc ument are the property of their respec tive owners Copyright c 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management NovencoBuilding IndustryA SisISO 9001 certified This means that all fans are inspected and tested before leaving the production 13 Warranty No...