13 Fuses
Operating Manual 90° ACTUSAFE CMF(S)QT
OM-ENGLISH-Failsafe-QT-16xx-V2.00-2022.03.01
13
Fuses
The Logik board of the controller cover (see Figure 87, page 76) features two miniature fuses for the control lines.
FL2
FL1
Figure 87:
FL1. . . fuse for auxiliary supply, FL2. . . fuse for the binary outputs
Fuses on the logic board
Fuse
Value
Manufacturer
No. of spare parts
FL1
1AT
Littelfuse 454 NANO
2
Slo-Blo
®
slow
FUSE-F1
FL2
4AT
Littelfuse 454 NANO
2
Slo-Blo
®
slow
FUSE-F2
NOTE:
The frequency inverter is protected by an input fuse and the explosion-proof version also has a thermal fuse (see
14
Spare parts
When ordering spare parts, please provide us with the serial number of the actuator (see section 2.2, page 23). Check the
separate break-down image and separate list of spare parts.
15
Lubricant recommendation, lubricant requirements
CAUTION:
Please note, that safety precautions such as the use of personal protective equipment (PPA) may
have to be followed! Please consult the safety datasheet (in section 8) of the product in question.
15.1
Main body: -25 to +60°C
Operating oil: DIN 51 517-CLP-HC
i.e. fully synthetic high-performance gear oils based on poly-alpha-olefins (PAO)
Viscosity class:
320 ISO VG
Pourpoint:
< -39°C (according DIN ISO 3016)
Lubricant requirement CM03:
200. . . 250 ml
Lubricant requirement CM06:
300. . . 350 ml
Lubricant requirement CM12:
600. . . 650 ml
15.2
Main body: -40 to +60°C
Operating oil: DIN 51 517-CLP-HC
i.e. fully synthetic high-performance gear oils based on poly-alpha-olefins (PAO)
78