20 Technical data
Operating Manual 90° ACTUSAFE CMF(S)QT
OM-ENGLISH-Failsafe-QT-16xx-V2.00-2022.03.01
20.7
Mode of operation CM
ON-OFF & INCHING operation
CM03
CM06
S2 - 15 minutes according to IEC 60034
S2 - 15 minutes according to IEC 60034
2,5 - 72 RPM
2,5 - 60 RPM
M
max
= 32 Nm
M
max
= 64 Nm
M
avg
= 16 Nm
M
avg
= 20 Nm
Life time*
10.000 cycles
10.000 cycles
MODULATING operation
CM03
CM06
S4 - 1.200 c/h - max. 50% DC according to IEC
60034
S4 - 1.200 c/h - max. 50% DC according to IEC
60034
2,5 - 36 RPM
2,5 - 30 RPM
M
max
= 32 Nm
M
max
= 64 Nm
M
avg
= 16 Nm
M
avg
= 32 Nm
Life time*
1.800.000 starts
1.800.000 starts
CONTINUOUS MODULATING operation
CM03
CM06
S9 - 1.800 c/h according to IEC 60034
S9 - 1.800 c/h according to IEC 60034
2,5 - 20 RPM
2,5 - 20 RPM
M
max
= 32 Nm
M
max
= 64 Nm
M
avg
= 10 Nm
M
avg
= 20 Nm
Life time*
1.800.000 starts
1.800.000 starts
*
NOTE:
life time is based on proper operation and maintenance according to SCHIEBEL operating manual
CYCLE
= 25 turns in both directions with at least 30% of nominal toque and the ability to accept 100% of nominal torque
for at least 10% of the stroke
START
= movement of at least 1% of stroke in both directions with a load of minimum 30% of nominal torque
88