Commissioning
©
by Antriebs- & Regeltechnik Schimpf GmbH
15
Configuring the analogue inputs and outputs
The analogue input (external setpoint input) as well as the analogue output
(position feedback) are usually set to 4-20 mA as standard.
00-10 only:
The analogue input and the analogue output can be used either in 4-20 mA or
0-20 mA operation.
00-15 and 01-15 only:
The analogue input and the analogue output can be used in current or voltage mode
(0/4-20 mA or 0/2-10 V).
DIP switch S15
on the base board must be set accordingly.
This DIP switch is used to switch the mode for position feedback between voltage and
current.
1: ON, 2: OFF; current (mA)
1: OFF, 2: ON; voltage (V)
The desired operating mode of the analogue interface must be stored in the device
settings in line with the instructions under menu item
in the section
1. The operating mode is set jointly for input
and output.
Calibration of the analogue inputs and outputs
The analogue input and the analogue output of the drive are calibrated at the
factory.
Recalibrating the analogue interface is usually only necessary if there are very
high requirements for angular accuracy or, for example, if the connection cables are
long. The calibration procedure is described in the section
under the menu items
Mode 2, Mode 3, and Mode 4
.