Operation
©
by Antriebs- & Regeltechnik Schimpf GmbH
55
Mode 0: Return to standard mode
Parameter 0:
Press and hold the “Prog” button to return the drive to standard mode.
Parameters 1-9:
Not assigned; when selected, the current setting is not changed
Mode 1: Test
Parameter 0:
The following LEDs are configured to stay on. They can be used to
determine if the device is working properly:
- LED
, green
- LED
, green
-
“PROG” LED, red
-
“Power” LED, green
-
“Enable” LED, green
-
“Error” LED, red
Parameter 2:
A plausibility check is performed for all settings. If an error is found in
any of the settings, the “Ready for operation” relay output drops out and the “Error”
LED will turn on. The flashing sequence of the “Auto/Enable” LED will indicate an error
number.
Flashing
Error description
2x
Drive position is outside the permissible range of motion
3x
Operating data setting error detected (analogue signal, direction of
rotation, torque, safe position, speed, averaging, ramp, hysteresis or
heating)
4x
Setting error detected in potentiometer calibration values
5x
Setting error detected in analogue output calibration values
6x
Setting error detected in analogue input calibration values
7x
General settings error