Technical specifications
©
by Antriebs- & Regeltechnik Schimpf GmbH
68
00-10/30 STEP
00-15/30 STEP
01-15/30 STEP
Operating mode:
Automatic electronic
control
•
Electronic control:
Input 0/4-20 mA
•
Up to 1000
steps/90°
•
Adjustable step
size
•
Adjustable
averaging for
analogue input
•
Adjustable safe
position
•
Enable signal
•
Adjustable ramp
•
Electronic control: Input 0/4-20 mA, 0/2-10 V
•
Up to 1000 steps/90°
•
Adjustable step size
•
Adjustable averaging for analogue input
•
Adjustable safe position
•
Enable signal
Adjustable ramp
Position feedback
Analogue output
0/4-20 mA
Analogue output
4-20 mA, 0/2-10 V
Position feedback
•
Current value transmitter (optional):
Potentiometer 0
– 1 K
Feedback outputs
•
2x end position relays potential-free min/max
•
Optional 2x freely adjustable cam switches,
potential-free
•
1x status relay output potential-free
•
2x end position
relays potential-
free min/max
•
Optional 3x freely
adjustable cam
switches, potential-
free
•
1x status relay
output potential-
free
Electrical
specifications of the
inputs and outputs
Position feedback analogue
:
•
Current source: Max. output voltage 12 V,
max. load 500
•
Voltage source: Max. output voltage 12 V,
max. current 30 mA
Setpoint input analogue
:
•
Max. input voltage:
12 V, current input: Load: 500
Relay outputs:
•
AC switching capacity:
Max. 250 V, 500 mA, resistive load
•
DC switching capacity:
max. 220 V, 500 mA, resistive load
Cam switch:
•
AC switching capacity:
Max. 250 V, 500 mA, resistive load
Max. 250 V, 250 mA, inductive load
•
DC switching capacity:
30 V, 1000 mA, resistive load
Max. 125 V, 100 mA, resistive load
30 V, 500 mA, resistive load
Max. 125 V, 30 mA, resistive load
3-point step, enable signal inputs:
•
AC version:
90..260 V AC, max. current 5 mA
•
DC version:
18..30 V, max. current 10 mA
Other product
features
•
Mechanical position indicator in the cover
•
Heating with thermostat