Schindler 3100/3300/6300
J 43402603 / 01
178/269
Copyright © 2017 INVENTIO AG
Remark
No
Step
0
The inspector must have the two test plugs
TEST-MGB
and
TEST-MGB1
(Brake Test Connectors) in his tool box. The plugs are not delivered with the
elevator.
Make sure the load measuring device is enabled.
The ‘Single Brake Test Up’ must not be performed if the ‘Full Brake Test
Up’ was not passed.
No
Step
1
Active 'Test Mode'
–
Press
'OK'
[10/__/_0]
–
Select
'Test mode'
[20/__/__]
–
Press
'OK'
[20/__/_0]
–
Activate
'Test mode'
[20/__/_1]
–
Press
'OK'
[20/__/_1]
The car travels to the control cabinet floor and opens the door.
The door remains open
[__/__/--]
2
Select 'Single Brake Test Up'
–
Select
"Start 'Single Brake Test Up"
[__/__/65]
–
Press
'OK'
[65/__/_1]
The door closes
The car travels to the bottom floor
The door remains closed
"Test ready to run"
[65/__/_2]
3
Prepare 'Single Brake Test Up'
–
Plug the "TEST-MGB" connector into the "MGB-T" socket at control
cabinet on the SNGL or SEM3x PCB)
Attention:
Monitor LUET after plugging in the MGB connector. If LUET is cleared the
car started to move unintended and the MGB connector must be removed
immediately. The elevator can remain in operation AND the replacement of
brake system is mandatory within next 4 weeks.
–
HMI display shows [65/__/_2]
4
–
Press
OK
–
The system checks if the "TEST-MGB" connectors is inserted
–
HMI display shows [65/__/_3] = "Test Single Brake Up" ready to start
5
Start 'Single Brake Test Up'
–
Press
’OK’
–
The car starts a trip to the top floor
–
HMI display shows a blinking "65"
[65/__/__]
–
The car reaches rated speed
–
HMI display shows a blinking "65"
[65/__/_1]
–
The controller triggers an emergency stop below the KSE-U magnet
–
HMI display shows [65/__/_4]