Schindler 3100/3300/6300
J 43402603 / 01
95/269
Copyright © 2017 INVENTIO AG
Persistent Fatal Rest
Reset Procedure for Persistent Fatal Error [25788; 23.08.2017]
4.9.3.2
Synchronization Travel
The elevator uses the synchronization mode to initialize the shaft information. A
synchronization travel will be triggered automatically in the following situations:
–
at system power up
–
after reset
–
after inspection travel
–
after installation travel mode
–
when a hoistway information recoverable error has occurred
The synchronization travel sequence will differ depending on the starting position of the
car. At the end of the synchronization trip, the car remains stationary at the lowest level
and the system returns to normal operation.
No
Step
1
On HMI dispatch a fatal error reset command to ACVF and control with special
command 101.
This clears persistent fatal errors related to pre-opening, releveling, KB/KB1,
safety circuit, PHSx bridging.
2
Press the “RESET” button on the SCPU PCBA.
Reaction:
The elevator starts up and performs a synch travel.
This procedure clears:
–
Persistent fatal error of the bionic control (pre-opening, re-leveling,
KSE, KNE, PHSx bridged, safety circuit)
–
Persistent fatal error of the ACVF (for example KB/KB1)
–
Activated fire service, activated firefighter floor.
–
Door lock monitoring condition
A
SCIC/SCPU: RESET
A