2.3
WHAT EVENTS COME FROM A SCHLAGE READER
The following events are communicated from the Schlage Readers.
VALID CARD
– is generated when a card is presented and is authorized by the Galaxy 635 Controller
INVALID CARD
– is generated when a card is presented at the reader that does not have authorization
to enter that door/or is not authorized at that time (access group/schedules in the Galaxy panel apply).
NOT IN SYSTEM
– is generated when a card is not known or loaded to the Galaxy controller receives
the card read from an AD-400 PIM
DOOR FORCED
– is generated when the door is opened by KEY OVERRIDE (i.e. using a key to open the
door instead of a credential). A door forced event is also generated if the door is forced open without
using a key or credential.
REQUEST to EXIT
(REX) – is generated by moving the inside door handle/lever.
NOTICE:
The outside door lever is always movable and always generates an REN event, regardless of
the door status, door schedule, or access rules (authorized/denied) of the credential. However, the
door cylinder should only retract (open) when a valid access condition is met (i.e. door is unlocked, or
credential is authorized, or operator sends door pulse or unlock command).
PIM TAMPER ALARM EVENT
– can be generated if a
PIM tamper switch
is activated that is wired to a
Galaxy Input/Output Board (DIO) and has been configured in the System Galaxy software to behave as
an alarm condition. See the main SG Software User Guide for instructions on configuring inputs and
outputs to trigger alarms.
System Galaxy Integration to Schlage AD400/AD300
Page 21