1.4
UPDATING OR EXPANDING EXISTING SYSTEMS
NOTICE:
Legacy
Wireless 485-PIM-ODT & WAPMs
are still supported in SG 10.2; however the Galaxy
CPU must be flashed up to 5.0 – if you are upgrading from SG 8 or 9, you may want to contact dealer
technical support to ensure you properly step through the hardware flash upgrade.
1.4.1
ADDING AD400’S TO AN EXISTING LEGACY SYSTEM
a)
DEDICATED NETWORK: You can install AD400 wireless hardware onto a separate DSI section
. In this case
you must configure the
Serial Channel programming
(in SG software) to use the Network Type = AD400
(wireless only) for the both new
AD400 network bus
as well as the
legacy Schlage ODT bus
. The addressing
requirements must meet specifications – see the following sections on addressing AD400 PIMs and Readers.
b)
SHARED NETWORK: You can install the AD400 wireless hardware onto the same network bus with the
existing legacy PIMs and Readers as long as you do the following:
•
You must assign unique AD400 PIM addresses that do not duplicate the ODT PIM addresses.
•
You must assign unique addresses to AD400 Readers that do not duplicate the legacy readers on the
network bus.
•
You cannot cross-link the equipment: Legacy readers can only link to legacy PIMs and visa-versa, AD400
readers can only link to AD400 PIMs.
•
You must set the Network Type to “AD400 (wireless only)” on the
Serial Channel
(in SG software).
1.4.2
ADDING AD300’S TO AN EXISTING AD400 SYSTEM
a)
DEDICATED NETWORK: You can install AD300 hardwired readers onto a separate DSI section
. In this case
you must set the Network Type to “AD300 (hardwired only)” the
Serial Channel
(in SG software) for the new
AD300 network bus
. Note: It is a requirement that even hardwired readers have a PIM address. Therefore
the
SG software auto-assigns a
PIM number
to the Reader that matches the binary address of the AD300 Reader.
b)
MIXED NETWORK: You can install the AD300 hardwired reader onto the same network bus with existing
AD400 wireless hardware as long as you do the following:
•
You must address the AD300 Readers to a binary value that is not used by any AD400 readers on the same
network bus.
•
You must use treat the binary address of an AD300 reader its own PIM number; and therefore you cannot
give the same binary address to an AD300 Reader and an AD400 PIM.
[Example: if an AD300 Reader is addressed to “4”, then there cannot be any AD400 PIMs addressed to 4].
•
You must set the Network Type to “AD300 & 400 (mixed-network)” on the
Serial Channel
(in SG software).
See other sections in this guide for diagrams of the mixed-networks and dedicated networks. Also
See
Creating a “Mixed-Network” Channel and Creating an AD300-Only Channel
for step-by-step
instructions.
System Galaxy Integration to Schlage AD400/AD300
Page 8