These products have been successfully tested and evaluated by UL
in two separate categories for use in both the United States and
Canada.
Auxiliary Lock. The GWXT fire listing qualifies the
M390RFK lock for use with UL Classified fire doors
maximum 4’ in width and 8’ in height, rated up to and
including 3 hours.
Component for use in Special Locking Arrangements.
Additionally, these products are qualified components
for the purpose of locking outward-swinging exit doors against
unauthorized egress.They are designed to release automatically
in case of a power failure or upon activation of an automatic fire
alarm system wired to the power supply fire panel relay.
These models have also been independently
tested to the ANSI/BHMA A156.23-2010 American
National Standard for Electromechanical Locks.
Holding Force:
1500lbf
Cycle Test:
Grade 1 = 1 million cycles
4
Power Supply:
NOTE:
All Schlage electromagnetic locks must be powered with a Listed filtered and regulated DC power supply such as the Schlage PS900 Series
of UL Listed power supplies.
Schlage offers a full line of power supplies and switching devices that are suitable for use with the M390RFK lock.
Specifications
MECHANICAL
(Including 1/4” [6.4mm] mounting bracket)
:
M390RFK Lock Dimensions:
1-5/8”D x 2-7/8”W x 10-1/2”L (41mm x 73mm x 268mm)
Armature
Dimensions:
5/8”D
3/4”D x 2-11/16”W x 10-3/8”L
Plate:
Housing:
x 2-3/8”W x 7-7/16”L (16.5mm x 61mm x 190mm)
ENVIRONMENTAL:
Not
M390RFK CURRENT REQUIREMENTS:
12VDC
650 milliamps
24VDC
450 milliamps
0-100’ 200’ max 300’ max
12VDC
16 Gauge 12 Gauge 12 Gauge
24VDC
18 Gauge 18 Gauge 16 Gauge
for use in outdoor environments.
Circuit board operating temperature:
14 to 140˚F (-10 to 60˚C)
ELECTRICAL:
Voltage:
Auto sensing 12VDC or 24VDC
Current:
0.65A at 12VDC
0.45A at 24VDC
MBS Output Relay*:
SPDT relay. Contacts rated at 1.25A at 24VDC
DSM Reed Switch*:
Magnetically actuated SPDT switch.
Contacts rated for 0.20A at 12VDC and 0.12A at 24VDC
*
Effective for either resistive or inductive loads
(power factor
≥
0.6 with inductive loads)
NOTE:
Specifications may change without notice.
*NOTE:
Wire gauges shown reference the load of a
single M390RFK electromagnetic lock.
Voltage
M390RFK
12VDC
0.65A
24VDC
0.45A
The Following Conditions of Acceptability Apply:
1)
This product is intended for use with Special Locking
Arrangements which are installed in accordance with the
manufacturer’s installation and operation instructions, the Life
Safety Code, NFPA 101 of the National Fire Protection Association
and the local authority having jurisdiction.
2)
The power for this unit is to be provided by a Listed (ALVY, ALVY7
FULA, FULA7, FUPPC, UEHX7, APHV or APHV7) Class 2 power supply
when designated as a Special Locking Arrangement (FWAX or FWAX7).
3)
The suitability of the lead wires is to be evaluated per the
requirements for the end-use product.
4)
When this product is installed in conjunction with a fire alarm
control panel, the wiring from the control unit to this product
device shall be for fail-safe operation.
5)
For Canadian Installations, this product is to be installed in
accordance with the manufacturer’s installation and operation
instructions, The Canadian Electrical Code C22.1-02, and the local
authority having jurisdiction.
6)
To qualify for use in a delayed-egress locking system, the relock
delay must be set to 0 seconds.
Burglar Alarm System Unit.
Note:
These locks are not intended or tested for use as a UL Listed