Form 57032 Rev. A
01-05-2004
8
VIP 5100 OPEN ARCHITECTURE CYLINDRICAL LOCK
INSTALLATION MANUAL
FIELD WIRING FROM
PANEL AND POWER
SUPPLY.
DOOR SWITCH
REX INPUT
(PLUG IN WHEN INSIDE
ESCUTCHEON IS
INSTALLED)
8. MAKE WIRING HARNESS CONNECTIONS :
A. Plug MAIN WIRING HARNESS into PC board.
B. Plug MAKE FIELD CONNECTIONS TO TERMINAL BLOCK.
C. Pug in DOOR STATUS SWITCH as shown.
D. Verify correct lock type setting (FSE/FSA) - see dip switch setting. Note: as ordered from the factory.
E. If lock is the one farthest away from PIB set termination resistor to “on”. All others should be in the “off/parked” position.
F. Test operation of inside lever to make sure that latch retracts fully.
IMPORTANT!
See PIB manual for additional connecting instructions.
SHIELD
DATA B
DATA A
GROUND
V+
1.0A @ 12VDC
0.5A @ 24VDC
OUTSIDE
MAIN HARNESS
CONNECTION
OFF
(PARKED)
ON
TERMINATION
RESISTOR:
1:
LOCK ADDRESS (SEE CHART)
2:
LOCK ADDRESS (SEE CHART)
3:
ALWAYS SET TO OFF
4:
ALWAYS SET TO OFF
5:
OFF = FAIL SECURE (FSE)
ON = FAIL SAFE (FSA)
6:
OFF = ALL
MG
LOCKS
ON = ALL
PX
LOCKS
7:
NOT USED
8:
NOT USED
9:
NOT USED
10:
NOT USED
LOCK
ADDRESS
1
LOCK
ADDRESS
2
LOCK
ADDRESS
3
LOCK
ADDRESS
4
DIP SWITCH
1
OFF
ON
OFF
ON
DIP SWITCH
2
OFF
OFF
ON
ON
DIP
SWITCH
NUMBER:
Note:
Lock addresses must be used in sequence and cannot
be the same for any two locks connected to a PIB. For
example, if the system has three locks, use addresses
1, 2, and 3 (but not 4). Lock address will correspond to
panel address on the PIB.