(1)
Only the first alert is flagged
Input overcurrent thresholds can be changed at the < Inputs > tab
Outlet overcurrent thresholds can be changed at the < Outlets > tab
General alert setting can be changed at the < System > tab
input voltage drop
alert
(1)
This alert occurs when the voltage on an input/line/phase drops below normal operating range,
even if the drop is very short (30ms).
When multiple inputs are in alert state, only the alert which appeared first is shown.
0 = OK , “3” means that there was an input/line/phase voltage alert at phase 3
outlet current drop
alert
(1)
Outlet drop alert raised for outlet number ..n.. .
When multiple outlets are in alert state, only the highest outlet will be indicated.
0 = OK , “22” means that there was a current drop at outlet “22”
input current drop
alert
(1)
Input current drop alerts occur due to a sudden current drop for an input. When multiple inputs are
in alert state, only the highest input will be indicated.
‘0’ is the indication of proper functioning.
sensor change
alert
(1)
Sensor change alerts occur when a sensor type has been changed. If multiple sensor types have
been changed the lowest sensor channel will be shown.
‘0’ is the indication of proper functioning.
outlet voltage drop
alert
(1)
Outlet voltage drop alerts occur for outlet number ..n.. .
When multiple outlets are in alert state, only the highest outlet will be indicated.
The threshold is set on 80% of the provided input current. This ensures proper functioning in
different countries.
0 = OK , “22” indicates a current drop at outlet “22”
Page 25 of 58
V262_User manual
Schleifenbauer PDU