I
NPUTS
–
TAB
#
This indicates the number of input phases. In this example, there are three inputs because a three
phase PDU is shown. A single phase PDU will show only one input.
name
By default, the name field has an eight character limit. With the “extended name”-option
enabled, you can make use of 18 characters. Whether users are allowed to modify names
depends on their user role according to the “permission model”
➢
See also chapter: “web interface > permission model” & “
kWh total
Total amount of energy per line. Important: These values can not be reset during the lifetime of
the devices.
subtotal / reset
Total amount of energy per line since the last reset. This value is reset by “unlocking” and clicking
the “reset” button.
power [VA]
Apparent power per line
power [W]
Real power per line
PF
Power factor per line [%] = real power [W] / apparent power [VA]
current
Actual current [A] per line
peak current
Highest current per line since the last “reset peaks and dips”
➢
See also chapter:
voltage
Actual voltage [V] per line
min voltage
Lowest measured voltage (dip) [V] since the last “reset peaks and dips”
➢
See also chapter:
overcurrent alert
at
Field in which the maximum current [A] is configured for this line, what the actual current is
allowed to reach. Exceeding this limit will cause an alert.
➢
See also chapter: System tab >
Page 28 of 58
V262_User manual
Schleifenbauer PDU