system-wide outlet
delay [msec]
Value for delay time between two switch actions in milliseconds. The default value is 100
milliseconds. Please note that values below 100 milliseconds are not accepted.
power up/down
outlet behaviour
Auto shut down is factory default on Schleifenbauer PDUs. When power distribution to the PDU
fails, all outlets will shut down; which of course leads to shut down of connected servers and
other equipment. The function of the auto shut down is to prevent peak currents damaging
equipment when the power loss is resolved and power distribution restarts. As a customer you
are able to set the power up mode of the outlets.
Outlet behaviour can be set as:
❏
no switching on power up
- at power up, all outlets are kept in the off state. This results in the PDU booting
up while any power draw on connected devices is prevented.
❏
use system-wide outlet delay
- at power up, all the outlets are set one by one to their last known state by
respecting the fixed
system-wide
outlet delay
❏
use individual outlet delay
- at power up, all the outlets are set to their last known state, but delayed by the
individual
outlet delay plus fixed
system-wide
outlet delay
Please note that an auto shut down will be performed in these three modes. This means all
outlets have been switched off in case of power loss.
For PDUs built from February 2018 equipped with 6-channel outlet prints, there is an extra
option:
❏
no switching on power down
- in this state outlets are not turned off by default on power loss. This option is only
available for G3 (2018) hardware.
outlet unlock
override
Setting for overriding the outlet unlock registers. When this setting is enabled outlets can be
switched or power cycled without unlocking them first.
Note that this makes it easier for the user to switch outlets using SNMP, Modbus and API, but also makes it easier to
switch the wrong outlet.
Please keep in mind that this setting isn’t valid for the web interface. To be able to make a change through web
interface, the relevant part has to be unlocked first.