How to change factory passwords?
How to change the Ethernet link settings?
The “ethernet link speed and duplex mode”-setting is set to
auto negotiate
by default. The link speed and duplex mode
are automatically configured with the link partner (e.g. Network Switch).
You can also configure the link speed and duplex mode to a fixed setting. You can choose from the following options:
●
Autonegotiate
●
10 Mbps Full Duplex
●
10 Mbps Half Duplex
●
100 Mbps Full Duplex
●
100 Mbps Half Duplex
We advise our customers to change all standard passwords during setup of the system to prevent
unauthorized access.
In the tab “Interfaces”, section “User management”, passwords can be changed.
There are five login profiles:
1. Viewer = viewing only
2. User = resetting alerts and switching outlets
3. Power = user + resetting subtotals
4. Admin = all administrator rights
And the ”factory profile”: Super
When this setting is changed, make sure the configuration of the link partner is changed accordingly!
Deviations in speed/duplex modes prevent users from connecting to the PDU remotely.
If this setting is changed to an invalid value by accident and users are unable to connect, change the setting
of the link partner to the same setting in the PDU to be able to access the PDU again. If this doesn’t solve the
problem: Try a
.
Page 42 of 58
V262_User manual
Schleifenbauer PDU