auto reset alert (s)
In this drop-down menu, the user chooses how much time it will take to
automatically clear alerts after the alert condition disappears.
Be sure that alerts are registered by your management software.
Settings
The available settings differ depending on the
PDU model. The settings on your PDU can
differ from the settings shown in the image.
display backlight
timeout
Setting for switching off display backlight after certain set time:
display orientation Setting for the orientation of the display on the PDU. This feature
allows the display orientation to be set correctly independent of the
mounting orientation of the PDU itself. It can be set as:
peak duration
[msec]
Configurable time in milliseconds a current overload is allowed to occur before an alert is given.
Note: we advise to prevent setting this time too short because this results in massive amounts of alerts.
current drop
detection
In this drop-down menu, you can select which current drops must be
detected. Please note that current drop detection is working as
follows: When the actual current of a channel (can be input or
metered outlet) is above 0.5A (500mA) and drops with more than 50%
of its value, then an input/ outlet current drop alert occurs.
For example:
●
Actual current = 0.4A, drops to 0A -> no alert
●
Actual current = 1A, drops to 0.6A -> no alert
●
Actual current = 1A, drops to 0.4A -> alert occurs