OPERATOR'S MANUAL 

 

14 

Subject to technical changes 

 

Schmalenberger GmbH + Co. KG 

D-72072 Tübingen / Germany 

Gateway 

Version: 27143 

 

6.5 

Counter-current system GSA with sensor button and FU 

The operator’s manual applies for the basic installation of the counter-current system  
27263 Xanas  and 27131 x-jet 
 
The GSA is connected to the gateway via “BUS”: 
 
Step 1: Bus wiring with 2-wire data cable, note chapter 6.3.2  
Step 2: Set MODE programme selector switch  

 

 
 
 
 
 
 
 

Figure 7 

 
In  order  for  the  gateway  and  converter  box  to  communicate  with  each  other,  a  device 
address must be set on the converter box using the MODE programme selector switch. 
 

Assignment of MODE programme selector switch to FU 

MODE 

FU 

FU1 

FU1 

FU2 

FU2 

FU3 

FU4 

 
 
     
 

 

MODE

MODE- 

Program selector switch 

Optional: Modbus data cable 

Summary of Contents for FLUVO 27143

Page 1: ...Gateway Operator s manual Translation of the original 27143 GB ...

Page 2: ...evices are not regular household waste In accordance with Directive 2002 96 EC of the European Parliament and Council of January 27 2003 regarding electrical and old electronic devices they must be disposed of properly Please drop these devices off at public collection points provided for that purpose when you have finished using them ...

Page 3: ... 3 2 Bus data cable 12 6 4 Overview of network capable devices via BUS 13 6 5 Counter current system GSA with sensor button and FU 14 6 6 Controlling the frequency inverter FU via Modbus 15 6 7 Attraction with sensor button and Control NT 16 6 8 LuchsNT light control via BUS 17 6 9 Light control via DMX 18 7 Start up 19 7 1 Procedure 19 7 2 Operating Display 19 7 3 Devices IP readout via myfluvo a...

Page 4: ...work and the attractions 1 1 Proper use The system may only be operated via the myfluvo app within the field of vision of the pool Any other use and operation is improper use Any resulting damage is excluded from liability 2 Functional features Ethernet interface via RJ45 plug IP parameters adjustable via web interface 24V DC voltage source for connection of 2x converter box RS485 interface for DM...

Page 5: ...unctions without delay Check the device and the electrical power line at regular intervals for damage The L N PE connection of the power supply voltage must be made in accordance with VDE 0100 and VDE 0160 A protective and isolating device must be provided for turning off the power supply Before beginning installation and service work the power supply connection must be switched off and secured ag...

Page 6: ... Terminal compartment disconnection Safety instruction The terminal compartment disconnection is a safety device for protecting loose connection cables against the mains voltage The terminal chamber disconnects are inserted and can be removed for easier wiring as follows Figure 2 Terminal compartment disconnection Installation is in the opposite order Terminal compartment disconnection ...

Page 7: ... to inactive A potential free latching switching contact must be used for closing In the delivery state this is closed via a wire jumper 3 BUS Interface for operating Fluvo devices via Fluvo BUS with communication LED The connection is protected against polarity reversal 4 RS485 DMX Master DMX signal output with communication LED Ensure correct polarity line A line B Ʇ shield 5 MODBUS Master FU si...

Page 8: ... GmbH Co KG D 72072 Tübingen Germany Gateway Version 27143 4 3 Device dimensions Dimensions in mm Figure 3 Cable gland M25 for LAN cable Sealing insert slotted for ø5 mm 6x cable gland M12 Control line Cable ø3 5 7 mm Cable gland M20 Power supply line Cable ø7 13mm ...

Page 9: ...rotection IP65 Only if unused cable screw connections are sealed with plugs Mains connection terminals Rigid cable cross section Flexible cable cross section with ferrule 0 2 2 5 mm 24 14 AWG Control contact connection terminals Rigid cable cross section Flexible cable cross section with ferrule 0 5 1 5 mm 20 16 AWG 0 5 1 0 mm Display LED GREEN LED RED Operation Service LAN Ethernet 1x RJ45 socket...

Page 10: ...erve the 4 2 enable contact description Mains power ON LED flashes 4x per second An initialisation process starts after 5 seconds The green and red LEDs flash alternately This procedure takes 30 seconds Red SERVICE Flashing for malfunction 5 1 Fault message If a fault message is present on a device connected via BUS this is indicated by the red service LED Error Flash code Measure Collective fault...

Page 11: ...ng The device has 6xØ5 5mm through holes for fixed wall mounting see Device dimensions chapter Figure 5 A cable gland 3 with a slotted sealing insert is provided for connecting the LAN cable Loosen the pressure screw and the sealing insert Thread the pressure screw and sealing insert over the assembled LAN cable Guide the assembled RJ45 plug through the opening into the terminal compartment and ti...

Page 12: ...nnection 6 3 1 Bus terminating resistor A terminating resistor can be set at each of the three bus connections via a slide switch TERM 6 3 2 Bus data cable To ensure stable data communication between the bus subscribers it is recommended to use a low capacitance shielded data cable for field bus systems The pair stranding and cable shield provides effective protection against external electromagne...

Page 13: ...l device address must be set on each SLAVE device Gateway LuchsNT BA 27142 Control NT BA 27248 Converter box BA 27251 24V GND DOUT DOUT DOUT DOUT BUS BUS Adjuster Devices AD Pos 1 0 Adjuster Devices AD Pos1 Pos2 Pos3 1 OFF OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF Adjuster Devices AD Pos Assignment A FU1 B FU1 C FU2 E FU2 E FU3 F FU4 During installation terminals A are connected to each other ...

Page 14: ...7131 x jet The GSA is connected to the gateway via BUS Step 1 Bus wiring with 2 wire data cable note chapter 6 3 2 Step 2 Set MODE programme selector switch Figure 7 In order for the gateway and converter box to communicate with each other a device address must be set on the converter box using the MODE programme selector switch Assignment of MODE programme selector switch to FU MODE A B C E E F F...

Page 15: ...03 Slave 4 FU 4 Adr 004 Modbus A RS485 A RS485 A RS485 A RS485 A Modbus B RS485 B RS485 B RS485 B RS485 B Connection cable with M12 connector A coded available with 10m length and open cable end For pure Modbus operation the following FU parameters must be set Kostal INVEOR setting parameters 6 051 SAS MODBUS baud rate 9600 6 065 MODBUS configuration 4 8 bits even parity 1 stop bit 32 bit big endi...

Page 16: ...rity reversal Set the corresponding device BUS ID for each Control NT device Each BUS ID may only be assigned once In the delivery state device 1 is active Pos1 Pos2 Pos3 1 OFF OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF Pos1 Pos2 Pos3 1 OFF OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF Pos1 Pos2 Pos3 1 OFF OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF Pos1 Pos2 Pos3 1 OFF OFF OFF 2 ON OFF OFF 3...

Page 17: ... 2 4 3 Note The connection is protected against polarity reversal Max line length 30 m Recommended control line 2 x 0 5 mm Make sure to set the BUS terminating resistor in the gateway Notice Observe 27142 LuchsNT operator s manual When operating LuchsNT via BUS on the gateway only the momentarily control function is possible The following is possible directly on the device ON OFF function only mom...

Page 18: ... a DMX input can be controlled via this output Each generation of LuchsNT RGB control units has a DMX input The gateway DMX master can be connected to this and then controlled via the myfluvo app Gateway Light control unit with DMX input When installing make sure that the polarity is correct DMX with DATA DMX with DATA Ʇ Data cable shield DMX start address 1 is permanently stored DMX channels 512 ...

Page 19: ...ted to the network either at the same time as the other devices or as the last of the devices If the gateway is connected to the mains before the bus subscribers the initialisation process is completed but these bus subscribers will only be recognised after the gateway has been restarted Alternative teach in functions during operation see chapter 8 2 1 7 2 Operating Display When the device is star...

Page 20: ...p 3 The automatic search function searches the network for an active gateway 4 If a gateway is found it is displayed with the current IP address Figure 9 The login password in the delivery state can be found on the device card or in the 4 2 Device specific data chapter 7 4 Device card The device card is located in the terminal compartment when delivered The MAC address device password and device s...

Page 21: ...This IP address is entered in the browser address bar and then this device overview opens Figure 10 The overview shows the possible devices to be connected Devices that were recognized during initialisation and are active are displayed in e g converter box 1 1 LuchsNT 1 1 If a device has been recognised but is currently inactive this is indicated as follows Converter box 0 1 LuchsNT 0 1 Inactive m...

Page 22: ...s are replaced or completely removed 8 2 2 Changing the myfluvo password Figure 12 In the delivery state the device password and the myfluvo password are identical To create an individual myfluvo password enter your desired new myfluvo password and confirm it by entering the device password The device password can be found in the terminal compartment under 4 2 device specific data or on the device...

Page 23: ...ateway Version 27143 Subject to technical changes Schmalenberger GmbH Co KG D 72072 Tübingen Germany 23 8 2 3 Device information Figure 13 8 2 4 Network settings Figure 14 In the delivery state DHCP is switched to active ...

Page 24: ...ter 6 5 and controls the associated FU via the analogue signal Up to 6 addresses can be set in the converter box via the programme selector switch The recognised device address is displayed with an The assignment to the FU can be read in the status of the converter box This information can be used to change the speed levels for example You can read out the current status of the device in the statu...

Page 25: ...er FU additional information The FU has a Modbus interface as standard By means of an optional connection cable see chapter 6 6 additional status information of the FU can be read out In this menu item it is possible to change the speed levels from 7 to up to 3 steps The change is implemented in the corresponding active converter box Figure 16 ...

Page 26: ...erger GmbH Co KG D 72072 Tübingen Germany Gateway Version 27143 8 5 DMX via i light This menu shows the current DMX output status DMX communication can be switched OFF or ON When switched off the DMX control function is not offered in the myfluvo APP Figure 17 ...

Page 27: ...OPERATOR S MANUAL Gateway Version 27143 Subject to technical changes Schmalenberger GmbH Co KG D 72072 Tübingen Germany 27 ...

Page 28: ...gsten Park Colletts Way Witney Oxfordshire OX29 0AZ United Kingdom www certikin co uk Manufacturer Schmalenberger GmbH Co KG Strömungstechnologie Im Schelmen 9 11 D 72072 Tübingen Germany Phone Fax Internet E mail 49 0 7071 70 08 0 49 0 7071 70 08 10 www fluvo de info schmalenberger de 2022 Schmalenberger GmbH Co KG All rights reserved Manual is subject to changes ...