OPERATOR'S MANUAL
Gateway
Version: 27143
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
17
6.8
LuchsNT light control via BUS
The LuchsNT control unit is connected to the gateway via BUS.
LuchsNT is automatically recognised on the gateway via the bus connection and displayed
via the “myfluvo ®” app.
All additional information on operation and installation can be found in the 27142
LuchsNT operator’s manual
Gateway
LuchsNT
Connection
terminals
BUS A
BUS B
Ʇ Shield
Data cable
Set BUS address
Device
Programme
selector
switch pos
1
0
2
1
3
2
4
3
Note:
The connection is protected against polarity reversal
Max. line length 30 m
Recommended control line 2 x 0.5 mm²
Make sure to set the BUS terminating resistor in the gateway.
Notice: Observe 27142 LuchsNT operator’s manual
When operating LuchsNT via BUS on the gateway, only the “momentarily” control function
is possible. The following is possible directly on the device:
ON / OFF function
only
momentarily
Change of colour momentarily
Button lighting setting 1-colour or RGB
The synchronisation bus is available for the operation of several control units with the
same control signal. A device is operated as MASTER to which the control signals are
connected. The remaining devices are operated as SLAVE,
for additional information,
see 27142 LuchsNT operator’s manual
.