Component Functions
EN-US · 30.30.01.02237 · 00 · 04/20
71 / 94
Value range
0x00 The data storage mechanism is not
permitted to write data to the con-
nected device.
0x01: The data storage mechanism is
permitted to write data to the con-
nected device.
0x00 The DS mechanism is not permit-
ted to read data from the connected
device.
0x01: The DS mechanism is permitted to
read data from the connected device.
Default value
0x00
Unit
—
EEPROM
no
Switch on/off sensor voltage L+
The sensor voltage L+ (Pin 1) can be switched on or off with the following parameter. By default, the volt-
age L+ is switched on after power-up, so that an IO-Link device can be automatically supplied with volt-
age when it is plugged in. With this parameter it is possible, for example, to use Pin 1 of the port as a dig-
ital output (refers to GND
S
= pin 3).
Offset parame-
ter
10414 (0x28AE)
Refers to IO-Link master 1 – Port X1
Description
Power on/off (switch L+ (pin 1))
Index
—
Data type
bool
Length
1 bytes
Access
Read/write
Value range
False: L+ power off
True: L+ power on
Default value
True: L+ power on
Unit
—
EEPROM
no
Switch on/off actuator voltage UA
The actuator voltage U
A
(Pin 2) can be switched on or off with the following parameter. By default, the
voltage U
A
is already switched on after power-up. In this case, ensure that 24 V is applied to this pin for
class A devices.
With this parameter it is possible, for example, to use Pin 1 of the port as a digital output (refers to GND-
A = Pin 5).
Offset parame-
ter
10415 (0x28AF)
Refers to IO-Link master 1 – Port X1
Description
Auxiliary power on/off
(switch UA (Pin 2))
Index
Data type
bool
Length
1 bytes
Access
Read/write
Value range
False: Auxiliary power off
True: Auxiliary power on
Default value
True: Auxiliary power on
Unit
-