INSTALLATION
30.30.01.00176/01
www.schmalz.com
EN | 31
All grounding wires for equipotential bonding must be provided with a green and yellow
cable. Minimum cross section 4 mm².
Procedure:
1. Crimped cable lug with eyelet for connecting the wires
2. Screw
3. Washers
4. Contact washer
5. Spring washer
6. Sticker for marking grounding
If there is no thread, use a self-locking hexagonal nut on the
other side.
5.3.2 Resistance measurement
Measure the total resistance once the installation is complete. The resistance between the measuring
points must not be higher than 10 ohm (the Schmalz definition of "low-resistance").
If the resistance is higher, check all the grounding connections.
Device component to be
grounded
1
1, 2
2