DESCRIPTION OF FUNCTIONS
www.schmalz.com
EN | 31
6.1.2.4
Reset of counters
This IO-Link system command is used to delete the two deletable counters in each ejector.
This IO-Link system command is used to delete the two deletable counters (ISDU parameters 143 and
144) in each ejector.
6.1.2.5
Reset of the maximum and minimum values for supply voltages
The minimum and maximum values of the two supply voltages for the sensor and actuator are
deleted.
6.1.3 Access rights
6.1.3.1
Extended Device Access Locks
In the extended device access locks parameter, there is the possibility to completely prevent NFC
access or limit it to read-only function:
ISDU
Dec
Parameter
Bit
Description
90
Extended device access locks
0
Parameters cannot be changed via NFC
1
NFC tag completely switched off
2
Firmware update for the ejectors is prevented
3
Manual mode locked for the ejectors
4
Prevention of creation of IO-Link events
The NFC lock using the extended device access locks parameter has a higher priority than
the NFC PIN. That means that this lock also cannot be bypassed by entering a PIN.
6.1.3.2
PIN code for NFC write protection
The writing of changed parameters via NFC can be controlled using a separate PIN code. When
delivered, the PIN code is 000 and a lock is therefore not active. The NFC PIN code can be changed
using IO-Link.
When a PIN code is set between 001 and 999, the valid PIN must be entered for every subsequent
write process using a mobile NFC device so that the SCTMi accepts the changes.
ISDU
Dec
Parameter
Value
Description
91
PIN code
0
PIN code for NFC write protection