18
Operating instructions
Solenoid interlock
AZM201
EN
6. Diagnostic functions
6.1 Diagnostic-LEDs
The solenoid interlock signals the operational state as well as errors
through three coloured LED’s installed on the front side of the device.
green
(Power)
Supply voltage on
yellow
(Status)
Operating condition
red
(Fault)
Error (see table: Error messages /
flash codes red diagnostic LED)
6.2 Solenoid interlock with conventional diagnostic output
The short-circuit proof diagnostic output can be used for central
visualisation or control functions, e.g. in a PLC.
The diagnostic output is not a safety-related output.
Error
Errors, which no longer guarantee the function of the solenoid interlock
(internal errors) cause the safety outputs to be disabled immediately.
Any error that does not immediately affect the safe functionality of the
solenoid interlock (e.g. excess ambient temperature, safety output to
external potential, short circuit) will lead to a delayed shut-down (refer
to table 2).
After fault rectification, the sensor can be reset by opening and
relocking the relevant guard door. The safety outputs enable and allow
a restart. An interlocking chain must be permanently "locked" to enable
the reactivation.
Automatic, electronic locking takes place if more than one
fault is detected at the safety outputs or a cross circuit is
detected between Y1 and Y2. This means that normal fault
acknowledgement is no longer possible. To reset this type of
interlocking, the solenoid interlock must be isolated from the
power supply after elimination of the error causes.
Error warning
A fault has occurred, which causes the safety outputs to be disabled
after 30 minutes. The safety outputs initially remain enabled. This
signal combination, diagnostic output disabled and safety channels still
enabled, can be used to stop the production process in a controlled
manner. An error warning is deleted when the cause of error is
eliminated.
Behaviour of the diagnostic output (Version ...-1P2PW)
(Example: power to unlock version)
Input signal magnet control
IN
Normal sequence, door was locked
OUT
Door could not be locked or fault
OUT
Key
Safety guard open
Safety guard closed
Unlock safety guard
Safety guard locked
Locking time: 150 ... 250 ms,
typically 200 ms 250 ms,
typically 200 ms
Safety guard not locked or fault
Evaluation of the diagnostic output (Version ...-1P2PW)
SPS
SPS
AZM 200
AZM 200
I N
O U T
E 1 . 0
A 1 . 0
A 1 . 0
E 1 . 0
A 1 . 0
E 1 . 0
M 1 . 0
M 1 . 0
M 2 . 0
M 2 . 0
&
&
A 1 . 0
E 1 . 0
&
A 1 . 0
E 1 . 0
&
Door can be locked
Door can be locked
Power to unlock: IN = 0 = locking
Door is locked
Door is locked
Power to lock: IN = 1 = locking
AZM201