23
AZM201
Operating instructions
Solenoid interlock
EN
9.2 Wiring configuration and accessories
Function safety switchgear
Pin
configuration
of the
connector
Configuration
of the
removable
terminal
blocks
Colour code of
the Schmersal connector to
DIN 47100
Possible colour codes for more
commercially available connectors
based on IEC 60947-5-2
with conventional
diagnostic output
with serial
diagnostic
function
24 V
U
e
1
1
WH
BN
X1
Safety input 1
2
2
BN
WH
GND
GND
3
5
GN
BU
Y1
Safety output 1
4
7
YE
BK
OUT
Diagnostic output
SD output
5
9
GY
GY
X2
Safety input 2
6
3
PK
PK
Y2
Safety output 2
7
8
BU
VT
IN
Solenoid control
SD input
8
4
RD
OR
without function
–
6
View of the terminal block for ordering suffix -SK or -CC
View of the version with removable terminal blocks
Y1
Y2
OUT
GND
24V
24V
X1
X2
IN
AZM 200.-.-1P2P.
AZM201.-.-.-1P2PW-.
Y1
Y2
OUT
GND
24V
24V
X1
X2
IN
AZM 200.-.-SD2P.
AZM201.-.-.-SD2P-.
7
8
9
5
1
2
3
4
6
AZM 200.-.-1P2P.-.
AZM201.-.-.-1P2PW-.
Connector plug ST2 M12, 8-pole
5
8
4
3
2
1
7
6
Accessories: Pre-wired cables
Connecting cables with coupling (female)
IP67, M12, 8-pole - 8 x 0.25 mm²
Cable length
Part number
2.5 m
5.0 m
10.0 m
103011415
103007358
103007359
Further versions in other lengths and with angled cable exit are available upon request.