Operating instructions

Solenoid interlock

AZM400

EN

7.  Set-up and maintenance

7.1  Functional testing

The safety function of the safety components must be tested.  

The following conditions must be previously checked and met: 

1.  Check max. axial misalignment of actuator and solenoid interlock.

2. Check max. angle displacement.

3.  Make sure that it is not possible to lift the actuator in the Z axis above 

the extended bolt.

4. Check for tight installation of the actuator and the switch.

5. Fitting and integrity of the cable connections.

6. Check the switch enclosure for damage.

7. Remove particles of dust and soiling.

8.  For versions with emergency exit, the following should also be 

considered: It must be possible to open the guard system from within 

the hazardous area; it must not be possible that the guard system is 

blocked from the inside. 

7.2  Maintenance

In the case of correct installation and adequate use, the safety 

switchgear features maintenance-free functionality.

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check for tight installation of the actuator and the switch.

2.  Check max. axial misalignment of actuator and solenoid interlock.

3. Check max. angle displacement.

4.  Make sure that it is not possible to lift the actuator in the Z axis above 

the extended bolt.

5. Fitting and integrity of the cable connections. 

6. Check the switch enclosure for damage.

7. Remove particles of dust and soiling.

Measures must be taken to protect against manipulation or 

against the bypassing of safety device, for example, using an 

extra actuator.

Damaged or defective components must be replaced.

8.  Disassembly and disposal

8.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

8.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations.

Summary of Contents for AZM400

Page 1: ...ine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range...

Page 2: ...release fitted is not permissible Observe the additional information in the operating instructions of the Bowden cable release 2 2 Special versions For special versions which are not listed in the or...

Page 3: ...en max 0 6 A Required rated short circuit current 100 A External Device fuse rating 2 A Min open close cycle Motor 3 s with continuous operation min average cycle time 20 s Electrical data Safety outp...

Page 4: ...lenoid interlock 1 7 mm with max angle offset of 2 The actuating curves show the typical detection range of the actuator depending on the actuating direction 26 10 26 10 0 mm 0 18 18 mm X Y 1 7 mm 4mm...

Page 5: ...auxiliary power supply this is so the locking bolt can be released independently of the control inputs Then no other actions are required the safety and diagnostic units remain off System condition on...

Page 6: ...C1 Connector plug M12 8 pole A2 Emergency exit C2 Connector plug M12 5 pole B Locking bolt extended D RFID sensor 3 7 Actuator and accessories Actuator AZM400 B1 not included in delivery 63 63 7 4 77...

Page 7: ...cable Minimum test interval every 24 hours etc Block drive If the locking bolt does not reach the locked condition with the first attempt the AZM400 makes an autonomous attempt If the second attempt...

Page 8: ...this way the activated code is definitively saved For ordering suffix I1 the executed allocation of safety interlock and actuator is irreversible For ordering suffix I2 the teach in procedure for a n...

Page 9: ...Unlock Off On Flashes quickly 0 V 0 V 0 V 0 V Only I2 Actuator has been taught Manipulation protection time is running Unlock Flashes Off Off 0 V 24 V 0 V 24 V 1 after 30 min disabling due to fault 2...

Page 10: ...nance In the case of correct installation and adequate use the safety switchgear features maintenance free functionality A regular visual inspection and functional test including the following steps i...

Page 11: ...r codes for more commercially available connectors based on IEC 60947 5 2 2007 OUT2 Diagnostic output 2 1 WH BN E1 Control input 1 2 BN WH Not connected 3 GN BU Y1 Safety output 1 4 YE BK OUT1 Diagnos...

Page 12: ...ype test certificate 01 205 5467 00 15 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279...

Reviews: