3.  Mounting

3.1  General mounting instructions

Please observe the relevant requirements of the standards 

ISO 12100, ISO 14119 and ISO 14120.

Any mounting position.

The accumulation of fine-grained contamination in the area of the bolt is 

to be prevented.

In such a case it is therefore not advised to have vertical mounting, 

where the bolt goes upwards from below.

For the correct fixing of the solenoid interlock, the device is provided 

with two mounting holes for M6 screws.

The M6 screws should have at least the strength class 10.9. 

The tightening torque of the M6 screws is 8 Nm.

The safety component and the actuator must be permanently 

fitted to the safety guards and protected against displacement 

by suitable measures (tamperproof screws, gluing, drilling, 

pinning).

Actuating directions and switch distances

The AZM400 can be operated within the following tolerance limits:

X – axis: ± 4 mm

Y – axis: ± 4 mm

Z – axis:  Distance between actuator and solenoid interlock 1…7 mm 

 

with max. angle offset of 2°

The actuating curves show the typical detection range of the 

actuator depending on the actuating direction.

~-26

~+10

~+26

~-10

0

[mm]

0

~+18

~18

[mm]

 

 

... 

mm

±

 4 mm

 

±

 4 mm

The approach direction must only be from the X and Y 

directions.

The maximum distance of 7 mm between the actuator 

and the solenoid interlock must be maintained so that the 

stipulated clamping force and the safe clamping function is 

achieved according to SIL 3.

The construction of the guard door is to be designed so that it 

is not possible to move the guard system with the actuator on 

the Z axis so far that the distance between the interlock and 

the actuator is greater than 7 mm.

The safety equipment must be designed so that there is no 

crushing hazard due to the movement of the bolt.

Mounting of the solenoid interlock and the actuator

Refer to the mounting instructions manual for the corresponding 

actuator.

To avoid any interference inherent to this kind of system and any 

reduction of the switching distances, please observe the following 

guidelines:

•  Metal parts and magnetic fields near the safety interlock can affect the 

switching distance.

• Keep away from metal chips.

Summary of Contents for AZM400

Page 1: ...ine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range...

Page 2: ...release fitted is not permissible Observe the additional information in the operating instructions of the Bowden cable release 2 2 Special versions For special versions which are not listed in the or...

Page 3: ...en max 0 6 A Required rated short circuit current 100 A External Device fuse rating 2 A Min open close cycle Motor 3 s with continuous operation min average cycle time 20 s Electrical data Safety outp...

Page 4: ...lenoid interlock 1 7 mm with max angle offset of 2 The actuating curves show the typical detection range of the actuator depending on the actuating direction 26 10 26 10 0 mm 0 18 18 mm X Y 1 7 mm 4mm...

Page 5: ...auxiliary power supply this is so the locking bolt can be released independently of the control inputs Then no other actions are required the safety and diagnostic units remain off System condition on...

Page 6: ...C1 Connector plug M12 8 pole A2 Emergency exit C2 Connector plug M12 5 pole B Locking bolt extended D RFID sensor 3 7 Actuator and accessories Actuator AZM400 B1 not included in delivery 63 63 7 4 77...

Page 7: ...cable Minimum test interval every 24 hours etc Block drive If the locking bolt does not reach the locked condition with the first attempt the AZM400 makes an autonomous attempt If the second attempt...

Page 8: ...this way the activated code is definitively saved For ordering suffix I1 the executed allocation of safety interlock and actuator is irreversible For ordering suffix I2 the teach in procedure for a n...

Page 9: ...Unlock Off On Flashes quickly 0 V 0 V 0 V 0 V Only I2 Actuator has been taught Manipulation protection time is running Unlock Flashes Off Off 0 V 24 V 0 V 24 V 1 after 30 min disabling due to fault 2...

Page 10: ...nance In the case of correct installation and adequate use the safety switchgear features maintenance free functionality A regular visual inspection and functional test including the following steps i...

Page 11: ...r codes for more commercially available connectors based on IEC 60947 5 2 2007 OUT2 Diagnostic output 2 1 WH BN E1 Control input 1 2 BN WH Not connected 3 GN BU Y1 Safety output 1 4 YE BK OUT1 Diagnos...

Page 12: ...ype test certificate 01 205 5467 00 15 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279...

Reviews: