background image

7

AZM400

Operating instructions

Solenoid interlock

EN

4.  Rear side Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

The voltage inputs A1 (and H1 with the AZM400Z-ST2..), and the 

control inputs E1, E2 and E3 must have a permanent protection against 

over-voltage. The use of PELV  supply units according to IEC 60204-1 

is recommended. The safety outputs can be integrated into the safety 

circuit of the control system.

4.2  Control options in the normal operating mode

Due to the control inputs E1, E2 and E3 for controlling the guard locking 

function it is possible to use different control options to be able to drive 

the AZM400 with a different safety controller. The function of the control 

inputs is the same for both ST and ST2 versions.

Setting the operational control inputs according to the following table 

causes the interlock to unlock.

Input condition

Version P/P

Version P/N

E1

E2

E3

E1 = E2

E3

Lock

open

open

GND

open

open

Unlock

24 V

24 V

GND

24 V

GND

Use of safety outputs of the type P/P:

Safety controller

AZM400

P2

N

E1 (2)

E2 (8)

E3 (6)

Inp 2

Inp 1

P1

GND

24 V

24 V

Use of safety controls of the type P/N:

Safety controller

AZM400

Inp 1

P

N

E1 (2)

E2 (8)

E3 (6)

Inp 2

GND

24 V

The outputs used for the control must correspond to the 

Performance Level (PL) of the guard system.  

To achieve the PL e the control must have tested outputs as 

these are not tested by the AZM400.

Independent of the version used, the notes in the Operating 

Instructions of the used controller should be observed.

These could include:

- Shielded installed cable

- Minimum test interval every 24 hours

- etc.

Block drive

If the locking bolt does not reach the "locked" condition with the first 

attempt, the AZM400 makes an autonomous attempt. If the second 

attempt also fails, the AZM400 signals a fault (comp. table 2).

After a malfunction, condition of the control inputs has to be changed to 

allow the locking bolt to be driven out again.

When the guard system closes slowly, a block drive can occur if the 

actuator that is opening is not in front of the bolt being driven out (see 

Chapter "Operating equipment and distances").

Unlocking after Power On

If after switching on, the AZM400 is already in the locked position, the 

device must first be unlocked and then locked again. This is to verify 

the causality of the drive signals and to check the sufficient depth of 

the locking bolt. The yellow LED flashes after power-on in the locked 

position.

4.3  Requirements for the connected safety-monitoring module

•  Dual-channel safety input, suitable for 2 p-type semi-conductor 

outputs (OSSD)

The solenoid interlock cyclically switch off the safety output to test 

them. The safety-monitoring module therefore does not need to be 

equipped with a cross-wire short detection. The test impulse time of 

≤ 0.4 ms must be tolerated by the evaluation. The test impulse, the 

switch-off time of the solenoid interlock can be extended depending on 

the cable length and the capacity of the cable used. 

Configuration of the safety controller

If the solenoid interlock is connected to electronic safety-

monitoring modules, we recommend that you set a discrepancy 

time of 100 ms. The safety inputs of the safety-monitoring 

module must be able to blank a test impulse of < 1 ms. 

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in the 

online catalogue on the Internet: www.schmersal.net.

Summary of Contents for AZM400

Page 1: ...ine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range...

Page 2: ...release fitted is not permissible Observe the additional information in the operating instructions of the Bowden cable release 2 2 Special versions For special versions which are not listed in the or...

Page 3: ...en max 0 6 A Required rated short circuit current 100 A External Device fuse rating 2 A Min open close cycle Motor 3 s with continuous operation min average cycle time 20 s Electrical data Safety outp...

Page 4: ...lenoid interlock 1 7 mm with max angle offset of 2 The actuating curves show the typical detection range of the actuator depending on the actuating direction 26 10 26 10 0 mm 0 18 18 mm X Y 1 7 mm 4mm...

Page 5: ...auxiliary power supply this is so the locking bolt can be released independently of the control inputs Then no other actions are required the safety and diagnostic units remain off System condition on...

Page 6: ...C1 Connector plug M12 8 pole A2 Emergency exit C2 Connector plug M12 5 pole B Locking bolt extended D RFID sensor 3 7 Actuator and accessories Actuator AZM400 B1 not included in delivery 63 63 7 4 77...

Page 7: ...cable Minimum test interval every 24 hours etc Block drive If the locking bolt does not reach the locked condition with the first attempt the AZM400 makes an autonomous attempt If the second attempt...

Page 8: ...this way the activated code is definitively saved For ordering suffix I1 the executed allocation of safety interlock and actuator is irreversible For ordering suffix I2 the teach in procedure for a n...

Page 9: ...Unlock Off On Flashes quickly 0 V 0 V 0 V 0 V Only I2 Actuator has been taught Manipulation protection time is running Unlock Flashes Off Off 0 V 24 V 0 V 24 V 1 after 30 min disabling due to fault 2...

Page 10: ...nance In the case of correct installation and adequate use the safety switchgear features maintenance free functionality A regular visual inspection and functional test including the following steps i...

Page 11: ...r codes for more commercially available connectors based on IEC 60947 5 2 2007 OUT2 Diagnostic output 2 1 WH BN E1 Control input 1 2 BN WH Not connected 3 GN BU Y1 Safety output 1 4 YE BK OUT1 Diagnos...

Page 12: ...ype test certificate 01 205 5467 00 15 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279...

Reviews: