CAM Control
DOC_MAN_MEC_EFAS-CAM_#SEN_#AIN_#V1
Seite 13 von 56
Version: 2018 / 02
In special cases you may attach the earth wire straight to the module.
NOTE
Earth wires should be short and have a large surface (copper mesh). Refer to
https://de.wikipedia.org/wiki/ground_(electronics)
or a similar source for further details
Installation
EFAS I/Os mount on 35 mm x 7.5 mm rails to DIN EN 50022.
Position
Mount with rail horizontally with the modules' multiple socket connectors pointing away from the wall. To
ensure that enough air gets in through the ventilation slots, leave at least 20 mm to the top and 35 mm to
adjacent devices or cabinet surfaces. Leave at least 20 mm of lateral distance to third-party units and cabinet
surfaces.
Figure 3: Aluminium profile
Attach cable shield here
M3x5 bolt
connection