EFAS CAM Module
4.1.1
Supply voltage
Power supply to module I/Os
+
24 VDC -20%+25%
L- 0 V
4.1.2
Status LEDs
"Run" LED
The "Run" LED indicates the state of the EtherCAT ASICs.
State
LED flash code
Explanation
Init
Off
Initialising, no data exchange
Pre-Op
Off/green, 1:1
Pre-operational, no data exchange
Safe-Op
Off/green, 5:1
Safe operation, inputs readable
Op
Green, on
Operational, unrestricted data exchange
"IO" LED
The LED labelled "IO" indicates the state of the module's I/Os.
State
LED flash code
Explanation
Ok
Off
No error
Error
Red, 1x
Short circuit of outputs
Red, 2x
Low voltage (U load, CPU)
Red, 4x
Bus system watchdog control failure
Figure 10: Front view