CAM Control
DOC_MAN_MEC_EFAS-CAM_#SEN_#AIN_#V1
Seite 17 von 56
Version: 2018 / 02
3.2.3
CAN connector
The CAN bus connects to the front of the module by means of a 4-pole Molex Micro-Fit Connector 3.0
TM
.
Connector (supplier: Farnell)
43025-0400: female Micro FIT 3.0
43030-0010: crimp socket PK100
MOLEX-79516-1043-MICRO-PASS 4WAY CABLE ASSEMBLY 3M
You may use a CAN to USB adapter to connect the CAN bus to the programming PC. (Source:
You may also need to adapt the D-SUB connectors to Micro-Fit.
Pin
Function
1
2
CAN_L
3
CAN_GND
4
5
6
7
CAN_H
8
9
Housing
Earth (GND)
Information
Please note that both ends of CAN cables require a 120Ω termination between CAN_L and
CAN_H.
GND
CAN_
L
CAN_
GND
CAN_
H
Figure 7: 4-pole male to female CAN connector
Figure 8: CAN to USB adapter (Lawicel)