background image

6

Operating instructions

Solenoid interlock

MZM 100

MZM 100 B

EN

6.  Diagnostic functions

6.1  Diagnostic LED's

The MZM 100 signals the operational state as well as errors through 

three coloured LED’s installed on the front side of the device

green

Supply voltage on

yellow

Operating condition 

red

Fault (refer to table 2: Flash codes of the red diagnostic LED)

6.2  Solenoid interlock with conventional diagnostic output

The short-circuit proof diagnostic output OUT can be used for central 

visualisation or control functions, eg in a PLC

The diagnostic output is not a safety-related output!

Depending on the variant used, specific diagnostic signals are emitted 

(refer to table 1)

Error

Errors, which no longer guarantee the function of the MZM 100 solenoid 

interlock (internal error)s cause the safety outputs to be disabled 

within the risk time Any error that does not immediately affect the 

safe functionality of the MZM 100 solenoid interlock (eg the ambient 

temperature too high, interference potential at a safety output,  

cross-wire short) will lead to a delayed shut-down (refer to table 2)

After the rectification of the error, the error message is reset by opening 

the corresponding safety guard

Error warning

A fault has occurred, which causes the safety outputs to be disabled 

after 30 minutes The safety outputs initially remain enabled  

This enables the shutdown of the process in a controlled manner  

An error warning is deleted when the cause of error is eliminated

If more than one fault is detected at the safety outputs,  

the component will be electronically locked and a normal  

fault reset will no longer be possible

To reset this type of interlocking, the component must be 

isolated from the power supply after elimination of the error 

causes

Behaviour of the diagnostic outputs of the W and W2 variants

Input signal magnet control

IN

Normal sequence, door was locked

OUT

Door could not be locked or fault

OUT

Key

Safety guard open

Safety guard closed

Unlock safety guard

Safety guard locked

Locking time
typically: 100  150 ms 
max: 1 s

Safety guard not locked or 
fault

Evaluation of the diagnostic outputs of the W and W2 variants

SPS/PLC

MZM 100

I N

O U T

E 1 . 0

A 1 . 0

M 1 . 0

M 2 . 0

A 1 . 0

E 1 . 0

&

A 1 . 0

E 1 . 0

&

Door can be locked

IN = 1 = locking

Door is locked

Summary of Contents for MZM 100

Page 1: ...ively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual labelled with the caution or warning symbol above the country specif...

Page 2: ...e upon request or can be downloaded from the Internet at www schmersal com 2 4 Purpose The safety switchgears are classified according to ISO 14119 as type 4 interlocking devices The MZM 100 is designed for application in safety circuits and is used for monitoring the position of movable separating safety guards A door detection sensor monitors the closed condition of the safety guard The optional...

Page 3: ...se duration on input signal 1 0 ms With test pulse interval of 100 ms Classification ZVEI CB24I Countersink C1 Source C1 C2 C3 Electrical data Safety outputs Safety outputs Y1 and Y2 Switching elements normally open function 2 channel OSSD p type Fuse rating short circuit proof Utilisation category DC 13 Ue Ie 24 VDC 0 25 A Rated operating current Ie each max 0 25 A Leakage current Ir 0 5 mA Volta...

Page 4: ...tolerate internal functional tests of the solenoid interlock with cyclic switch off of the safety outputs for max 2 ms typically 1 ms The switch off stage of the test cycle is temporarily reduced by an active ohmic discharge of the cable If the safety sensor is connected to electronic safety monitoring modules we recommend that you set a discrepancy time of min 100 ms The safety inputs of the safe...

Page 5: ...prox 100 N To this end the adjustment target MZM 100 TARGET is used directly on the fitted MZM 100 Adjustment of the latching force 1 Open the safety guard and isolate the MZM 100 from the voltage supply Either switch off the voltage supply or pull out the connector 2 Put the adjustment target with the active side on the identification plate of the MZM 100 3 Switch the voltage supply of the MZM 10...

Page 6: ...cross wire short will lead to a delayed shut down refer to table 2 After the rectification of the error the error message is reset by opening the corresponding safety guard Error warning A fault has occurred which causes the safety outputs to be disabled after 30 minutes The safety outputs initially remain enabled This enables the shutdown of the process in a controlled manner An error warning is ...

Page 7: ...en 0 V On Off Off 0 V 0 V Safety guard closed actuator in safety guard can be locked 0 V On Off Flashes 24 V 24 V Safety guard closed and locked 24 V On Off On 24 V 24 V Solenoid interlock cannot be locked Safety guard not correctly closed or magnet soiled 24 V On Off Off 0 V 0 V Error warning1 actuator in 0 V 24 V On Flashes 2 flashes on 24 V 0 V Error 0 V 24 V On Flashes 2 Off 0 V 0 V 1 after 30...

Page 8: ... diagnostic channels are wired in series The diagnostic data are transmitted through the series wiring of the inputs and outputs Max 31 safety switchgear with serial diagnostics can be wired in series For the evaluation of the serial diagnostics line either the PROFIBUS Gateway SD I DP V0 2 or the Universal Gateway SD I U are used This SD Gateway is integrated as a slave in an existing field bus s...

Page 9: ...tatus signals and the safety outputs by means of an example of MZM 100 variant Solenoid interlock monitored System condition LED Safety outputs Response byte bit n green red yellow Y1 Y2 7 6 5 4 3 2 1 0 Safety guard open On Off Off 0 V 0 0 0 X 0 0 0 0 Safety guard closed actuator in On Off Flashes 0 V 0 0 0 X 0 0 1 0 Safety guard closed and locked On Off On 24 V 0 0 0 X 0 1 1 1 Solenoid interlock ...

Page 10: ...t safety component are wired to the safety monitoring module X1 Y1 X2 Y2 1 2 3 5 6 8 X1 X2 A1 A2 Y1 Y2 1 2 3 5 6 8 X1 4 Y1 4 Y1 X2 7 Y2 7 Y2 OUT A1 A2 OUT SPS PLC IN SPS PLC SPS PLC IN 24 VDC GND SPS PLC n participants Safety outputs evaluation Wiring example 2 series wiring of the MZM 100 with serial diagnostic function The safety outputs of the first safety component are wired to the safety moni...

Page 11: ...t 1 4 4 YE BK OUT Diagnostic output SD output 5 5 GY GY X2 Safety input 2 6 6 PK PK Y2 Safety output 2 7 7 BU VT IN Solenoid control SD input 8 8 RD OR without function 9 Connector plug ST M23 8 1 pole Connector plug ST2 M12 8 pole 1 2 9 3 4 5 6 7 8 5 8 4 3 2 1 7 6 Connecting cables with female connector IP67 M23 8 1 pole 8 x 0 75 mm Connecting cables with coupling female IP67 IP69 M12 8 pole 8 x ...

Page 12: ...6 2011 Notified body which approved the full quality assurance system referred to in Appendix X 2006 42 EC TÜV Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal December 2 2016 Authorised signature Philip Schmersal Managing Director ...

Reviews: