PROTECT-IE

Operating instructions
Input expander module

EN

Monitored inputs: 

Cross-wire detection (Y/N): 

 Yes

Wire breakage detection (Y/N): 

 Yes

Earth leakage detection (Y/N): 

 Yes

Number of NO contacts:

 

variant 02: 0; variant 11: 4

Number of NC contacts:

 

variant 02: 8; variant 11: 4

Conduction resistance:

 

max. 40 Ω

Outputs: 

Number of enabling paths:

 2

Number of auxiliary contacts:

 0

Number of signalling outputs: 

 4

Switching capacity of the enabling paths: 

13-14; 23-24:  

max. 24 V / 2 A ohmic (inductive  

with suitable protective circuit);  

min. 10 V / 10 mA

Recommended fuse for the enabling paths:

 

2 A slow blow

Switching capacity of the signalling outputs: 

Y1 … Y4: 24 VDC / 100 mA

Dimensions H x W x D:

 

126 mm x 48 mm x 61 mm

The data specified in this manual is applicable when the  

component is operated with rated operating voltage U

e

 ± 0%

.

2.5  Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508

PL:

 

STOP 0: up to d

Category:

 

STOP 0: up to 3

DC: 

STOP 0: > 60 % (low)

CCF:

 

 

> 65 points

PFH value:

 

STOP 0: 2.00 x 10

-7

/h

SIL:

 

STOP 0: up to 2

Service life:

 

20 years

The PFH value of 2.00 x 10

-7

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching cy-
cles (n

op/y

) mentioned in the table below. At 365 operating days per year 

and a 24-hours operation, this results in the below-mentioned switching 
cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

The above-described requirements cannot be met by the 
input expander module solely, but only in combination with a 
safety-monitoring module as described in this manual.

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted backwards in the DIN 
rail and push down until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 126 × 48 × 61 mm
with plug-in terminals: 126 × 48 × 53 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 
against unintentional contact of the connected and therefore 
electrically interconnected apparatus and the insulation of the 
feed cables must be designed for the highest voltage, which 
can occur in the device.

The electrical connection may only be carried out by authorised 
personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

•  U

B

: Status operating voltage (LED is on, when the operating voltage 

on the terminals is ON)

•  Y1…Y4: Status of the inputs S1…S8 (LED is on, when the allocated 

input circuit is opened)

5.2  Description of the terminals

Voltages:

A1

A2

+

S1 … S8

+24 VDC

0 VDC

24 VDC

0 VDC

+24 VDC / 0 VDC

Outputs:

13-14

23-24

1. 

Enabling circuit 

2. 

Enabling circuit 

Start:

Y1 … Y4

Status of the inputs (+24 V, when the 

allocated input circuit is opened)

S5

IE..

S1

S6

UB

+

+

+

+

Y2

S3

Y1

13

23

A2

S4

S7

24

A2

14

A1

A1

Y3 Y4

S8

S2

Fig. 1

Signalling outputs must not be used in safety circuits.

6.  Set-up and maintenance

6.1  Functional testing

The function of the component must be tested. The following conditions 
must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the switch enclosure for damage
4.  Check the electrical function of the connected sensor technology and 

their influence on the safety-monitoring module and the downstream 
actuators

Summary of Contents for PROTECT-IE Series

Page 1: ... product is ins talled must meet the provisions laid down in the paragraph Electromagnetic Compatibility EMC of DIN EN 60204 1 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further technical information can be ...

Page 2: ...control cabinets They are used for the evaluation of the signals of 1 4 sensors and the summarised transmission of the signals to a downstream safety monitoring module The function is defined as the opening of the enabling contacts 13 14 and 23 24 when one or more of the 8 sensor inputs are actuated The enabling paths with the outputs contacts 13 14 and 23 24 meet the following requirements under ...

Page 3: ...s described in this manual 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted backwards in the DIN rail and push down until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D 126 48 61 mm with plug in terminals 126 48 53 mm 4 Electrical connection 4 1 General information ...

Page 4: ...K1 K1 K2 K2 14 24 S6 13 23 A1 S4 S5 Y3 UB S7 S8 Y1 Y2 K1 K2 K3 K4 K5 K6 K7 K8 K1 K3 K5 K7 K2 K4 K6 K8 Protect IExx S12 S11 S22 S21 14 13 24 23 a Fig 3 a Safety monitoring module e g SRB 301MC SRB 301ST SRB 211ST 8 2 Sensor configuration Dual channel control of magnetic safety sensors to IEC 60947 5 3 see Fig 4 The control system recognises wire breakage and earth faults in the control circuit Cros...

Page 5: ...used inputs S2 S4 S6 and S8 remain vacant S1 S2 Y1 a S3 S4 Y2 S5 S6 Y3 S7 S8 Y4 Fig 9 a signal outputs 8 3 Actuator configuration Enabling circuits Fig 10 All safety monitoring modules with control category 4 or PLe from the Schmersal Group with current 1 A in the monitoring circuit can be connected to the Protect IE 02 and Protect IE 11 devices 13 23 14 24 S11 S21 S12 S22 13 23 14 24 a Protect IE...

Page 6: ... body which approved the full quality assurance system referred to in Appendix X 2006 42 EC TÜV Rheinland Industrie Service GmbH Alboinstraße 56 12103 Berlin ID n 0035 K A Schmersal GmbH Co KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www sch...

Reviews: