Operating instructions
Input expander module

EN

Dual-channel antivalent control of magnetic safety sensors to  
IEC 60947-5-3 (see Fig. 7)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 7 a) signal outputs

Dual-channel antivalent control of an emergency stop circuit to  
EN ISO 13850 and EN 60947-5-5 (Fig. 8)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 8 a) signal outputs

Dual-channel antivalent control of a guard door monitoring  
EN 1088 (Fig. 9)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 9 a) signal outputs

8.3  Actuator configuration
Enabling circuits (Fig. 10)

•  All safety-monitoring modules with control category 4 or PLe from the 

Schmersal Group with current < 1 A in the monitoring circuit can be 
connected to the Protect-IE-02 and Protect-IE-11 devices.

13

23

14

24

S11

S21

S12

S22

13

23

14

24

a)

Protect 

IExx

K1

K3

K5

K2

K4

K6

K7

K8

K1

K2

Fig. 10
a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST

The safety-monitoring modules must be suitable for the 
signal processing of single- or dual-channel potential-free NC 
contacts. The start and actuator configuration must be set up 
in accordance with the datasheet.

Signalling outputs (see fig. 11)

•  The LED's or the signal outputs indicate that the safety guard or the 

emergency stop circuit is opened.

•  Both contact circuits of a sensor are monitored.

•  If the safety guard or the emergency stop circuit is opened, a 24V 

signal is activated at the output concerned (Y1...Y4) and the allocated 
LED is lit.

Y1

Y2

Y3

Y4

K3

K5

K1

K7

K4

K6

K2

K8

A1

A2

Fig. 11

Cascading (Fig. 12)

•  In this way, up to 20 components can be wired in series. This 

 

corresponds to a signal processing of up to 80 sensors.

13

14

23

24

Pr

otect-IE..

Protect-IE..

Protect-IE..

Protect-IE..

13

14

23

24

13

14

23

24

13

14

23

24

S11

S12

S21

S22

a)

      

      

Fig. 12
a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST

Summary of Contents for PROTECT-IE Series

Page 1: ... product is ins talled must meet the provisions laid down in the paragraph Electromagnetic Compatibility EMC of DIN EN 60204 1 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further technical information can be ...

Page 2: ...control cabinets They are used for the evaluation of the signals of 1 4 sensors and the summarised transmission of the signals to a downstream safety monitoring module The function is defined as the opening of the enabling contacts 13 14 and 23 24 when one or more of the 8 sensor inputs are actuated The enabling paths with the outputs contacts 13 14 and 23 24 meet the following requirements under ...

Page 3: ...s described in this manual 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted backwards in the DIN rail and push down until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D 126 48 61 mm with plug in terminals 126 48 53 mm 4 Electrical connection 4 1 General information ...

Page 4: ...K1 K1 K2 K2 14 24 S6 13 23 A1 S4 S5 Y3 UB S7 S8 Y1 Y2 K1 K2 K3 K4 K5 K6 K7 K8 K1 K3 K5 K7 K2 K4 K6 K8 Protect IExx S12 S11 S22 S21 14 13 24 23 a Fig 3 a Safety monitoring module e g SRB 301MC SRB 301ST SRB 211ST 8 2 Sensor configuration Dual channel control of magnetic safety sensors to IEC 60947 5 3 see Fig 4 The control system recognises wire breakage and earth faults in the control circuit Cros...

Page 5: ...used inputs S2 S4 S6 and S8 remain vacant S1 S2 Y1 a S3 S4 Y2 S5 S6 Y3 S7 S8 Y4 Fig 9 a signal outputs 8 3 Actuator configuration Enabling circuits Fig 10 All safety monitoring modules with control category 4 or PLe from the Schmersal Group with current 1 A in the monitoring circuit can be connected to the Protect IE 02 and Protect IE 11 devices 13 23 14 24 S11 S21 S12 S22 13 23 14 24 a Protect IE...

Page 6: ... body which approved the full quality assurance system referred to in Appendix X 2006 42 EC TÜV Rheinland Industrie Service GmbH Alboinstraße 56 12103 Berlin ID n 0035 K A Schmersal GmbH Co KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www sch...

Reviews: