background image

4

Operating instructions
Input expander module

PROTECT-IE

EN

6.2  Maintenance

A regular visual inspection and functional test, including the following 
steps, is recommended:
1. Check the correct fixing of the input expander module
2. Check the cable for damages
3. Check electrical function

The device has to be integrated into the periodic check-ups 
according to the Ordinance on Industrial Safety and Health, 
however at least 1x/year.

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The input expander module must be disassembled in the  
de-energised condition only.

Insert a screwdriver at the marked position, press in the direction of the 
cover and remove.

2)

1)

61*

53**

Fig. 6:
1) Disassembly;
2) DIN rail system to EN 60715;
*  with cage clamps; 
**  with plug-in terminals (representation of the standard version 

PROTECT-IE-11)

7.2  Disposal

The input expander module must be disposed of in an appropriate  
manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

•  Start level: Depends on the wiring of the safety relay module

•  Sensor level: Dual-channel control of magnetic safety sensors to 

 

IEC 60947-5-3

•  Output level: dual-channel control of a downstream safety-monitoring 

module

F1

S1

S2

S3

A2

A2

Y4

+

A1

K7

K8

K5

K6

K3

K4

K1

K1

K2

K2

14

24

S6

13

23

A1

+

S4

+

S5

Y3

UB

+

S7

S8

Y1

Y2

K1/K2

K3/K4

K5/K6

K7/K8

K1

K3

K5

K7

K2

K4

K6

K8

Protect-IExx

S12

S11

S22

S21

14

13

24

23

a)

Fig. 3
a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST

8.2  Sensor configuration
Dual-channel control of magnetic safety sensors to IEC 60947-5-3 
(see Fig. 4)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be 

 

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 4 a) signal outputs

Dual-channel emergency stop circuit to EN ISO 13850 and  
EN 60947-5-5 (Fig. 5)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be 

 

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 5 a) signal outputs

Dual-channel guard door monitoring to EN 1088 (Fig. 6)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be 

 

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be 

 

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 6 a) signal outputs

Summary of Contents for PROTECT-IE Series

Page 1: ... product is ins talled must meet the provisions laid down in the paragraph Electromagnetic Compatibility EMC of DIN EN 60204 1 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further technical information can be ...

Page 2: ...control cabinets They are used for the evaluation of the signals of 1 4 sensors and the summarised transmission of the signals to a downstream safety monitoring module The function is defined as the opening of the enabling contacts 13 14 and 23 24 when one or more of the 8 sensor inputs are actuated The enabling paths with the outputs contacts 13 14 and 23 24 meet the following requirements under ...

Page 3: ...s described in this manual 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted backwards in the DIN rail and push down until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D 126 48 61 mm with plug in terminals 126 48 53 mm 4 Electrical connection 4 1 General information ...

Page 4: ...K1 K1 K2 K2 14 24 S6 13 23 A1 S4 S5 Y3 UB S7 S8 Y1 Y2 K1 K2 K3 K4 K5 K6 K7 K8 K1 K3 K5 K7 K2 K4 K6 K8 Protect IExx S12 S11 S22 S21 14 13 24 23 a Fig 3 a Safety monitoring module e g SRB 301MC SRB 301ST SRB 211ST 8 2 Sensor configuration Dual channel control of magnetic safety sensors to IEC 60947 5 3 see Fig 4 The control system recognises wire breakage and earth faults in the control circuit Cros...

Page 5: ...used inputs S2 S4 S6 and S8 remain vacant S1 S2 Y1 a S3 S4 Y2 S5 S6 Y3 S7 S8 Y4 Fig 9 a signal outputs 8 3 Actuator configuration Enabling circuits Fig 10 All safety monitoring modules with control category 4 or PLe from the Schmersal Group with current 1 A in the monitoring circuit can be connected to the Protect IE 02 and Protect IE 11 devices 13 23 14 24 S11 S21 S12 S22 13 23 14 24 a Protect IE...

Page 6: ... body which approved the full quality assurance system referred to in Appendix X 2006 42 EC TÜV Rheinland Industrie Service GmbH Alboinstraße 56 12103 Berlin ID n 0035 K A Schmersal GmbH Co KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www sch...

Reviews: