Operating instructions

Input expander module

PROTECT-IE

EN

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the input expander module

2. Check the cable for damages

3. Check electrical function

If a manual functional check is necessary to detect a possible 

accumulation of faults, then this must take place during the 

intervals noted as follows:

•  at least every month for PL e with category 3 or  

category 4 (according to ISO 13849-1) or SIL 3 with HFT 

(hardware fault tolerance) = 1 (according to IEC 62061);

•  at least every 12 months for PL d with category 3  

(according to ISO 13489-1) or SIL 2 with HFT  

(hardware fault tolerance) = 1 (according to IEC 62061).

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The input expander module must be disassembled  

in the de-energised condition only.

Insert a screwdriver at the marked position, press in the direction of the 

cover and remove.

2)

1)

61*

53**

Fig. 6:

1) Disassembly;

2) DIN rail system to EN 60715;

* with cage clamps; 

**  with plug-in terminals (representation of the standard version 

PROTECT-IE-11)

7.2  Disposal

The input expander module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

•  Start level: Depends on the wiring of the safety relay module

•  Sensor level: Dual-channel control of magnetic safety sensors to  

IEC 60947-5-3

•  Output level: dual-channel control of a downstream safety-monitoring 

module

F1

S1

S2

S3

A2 A2

Y4

+

A1

K7

K8

K5

K6

K3

K4

K1

K1

K2

K2

14

24

S6

13

23

A1

+

S4

+

S5

Y3

UB

+

S7

S8

Y1

Y2

K1/K2

K3/K4

K5/K6

K7/K8

K1

K3

K5

K7

K2

K4

K6

K8

Protect-IExx

S12

S11

S22

S21

14

13

24

23

a)

Fig. 3

a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST

8.2  Sensor configuration

Dual-channel control of magnetic safety sensors to IEC 60947-5-3 

(see Fig. 4)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be  

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 4 a) signal outputs

Dual-channel emergency stop circuit to ISO 13850 and  

EN 60947-5-5 (Fig. 5)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be  

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 5 a) signal outputs

Dual-channel guard door monitoring to ISO 14119 (Fig. 6)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  If the inputs S2, S4, S6 and S8 are not used, they have to be  

bridged to –.

S1

+

S2

Y1

a)

S3

+

S4

Y2

S5

+

S6

Y3

S7

+

S8

Y4

Fig. 6 a) signal outputs