5

PROTECT-IE

Operating instructions

Input expander module

EN

Dual-channel antivalent control of magnetic safety sensors to IEC 

60947-5-3 (see Fig. 7)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 7 a) signal outputs

Dual-channel antivalent control of an emergency stop circuit to 

ISO 13850 and EN 60947-5-5 (Fig. 8)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 8 a) signal outputs

Dual-channel antivalent control of a guard door monitoring  

ISO 14119 (Fig. 9)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the monitoring circuits are detected.

•  If the inputs S1, S3, S5 and S7 are not used, they have to be  

bridged to +.

•  The unused inputs S2, S4, S6 and S8 remain vacant.

S1

+

S2

Y1

a)

+

S3

+

S4

Y2

+

S5

+

S6

Y3

+

S7

+

S8

Y4

+

Fig. 9 a) signal outputs

8.3  Actuator configuration

Enabling circuits (Fig. 10)

•  All safety-monitoring modules with control category 4 or PLe from the 

Schmersal Group with current < 1 A in the monitoring circuit can be 

connected to the Protect-IE-02 and Protect-IE-11 devices.

13

23

14

24

S11

S21

S12

S22

13

23

14

24

a)

Protect 

IExx

K1

K3

K5

K2

K4

K6

K7

K8

K1

K2

Fig. 10

a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST

The safety-monitoring modules must be suitable for the 

signal processing of single- or dual-channel potential-free NC 

contacts. The start and actuator configuration must be set up 

in accordance with the datasheet.

Signalling outputs (see fig. 11)

•  The LED's or the signal outputs indicate that the safety guard or the 

emergency stop circuit is opened.

•  Both contact circuits of a sensor are monitored.

•  If the safety guard or the emergency stop circuit is opened, a 24V 

signal is activated at the output concerned (Y1...Y4) and the allocated 

LED is lit.

Y1

Y2

Y3

Y4

K3

K5

K1

K7

K4

K6

K2

K8

A1

A2

Fig. 11

Cascading (Fig. 12)

•  In this way, up to 20 components can be wired in series. This 

corresponds to a signal processing of up to 80 sensors.

13

14

23

24

Protect-IE..

Protect-IE..

Protect-IE..

Protect-IE..

13

14

23

24

13

14

23

24

13

14

23

24

S11

S12

S21 S22

a)

      

      

Fig. 12

a) Safety-monitoring module, e.g. SRB 301MC, SRB 301ST, SRB 211ST