Instruction Manual PROTECT-PSC
V 2.6R01 / 04.19
1
–5
1.4.1
Overview of the modules
The PROTECT-PSC system essentially consists of the following modules:
POWER Modul
, produces 3.3VDC from 24VDC and provides to CPU and In-
put/Output modules (PSC-Power, PSC-Booster).
CPU module
, responsible for processing the user program and controlling the
input/output modules (PSC-CPU-OP-MON, PSC-CPU-MON ).
Input/output modules
to record/control the states of externally connected
sensors/actuators (PSC-SUB-MON, PSC-S-STP-E, PSC-S-STP-LC, PSC-S-STP-
ELC, PSC-S-IN-E, PSC-S-IN-LC, PSC-S-OUT, PSC-S-Relais)
Non-Safety Input/Output modules
to record/control the states of externally
connected sensors/actuators (PSC-NS-IN, PSC-NS-OUT+)
All the above mentioned modules (with the exception of the back plane) have a
redundant structure with two 16 bit microcontrollers monitoring each other.
1.4.2
Brief data
•
Can be used in applications up to PL e, category 4 to ISO 13849-1.
•
In operating mode 3 programming can be done by ladder diagram (conform-
ing to IEC 61131).
•
Programming by means of Windows PC via USB interface
•
Safety and standard Inputs/Outputs are available in mode 3.
•
A maximum of 254 Input/Output channels are available.
•
Possibility to store documentation / comments.
•
Monitored 24 VDC power supply .
•
Input/output modules with self-monitoring.
•
Connection facilities:
Sensor level:
EMERGENCY-OFF (EMERGENCY-STOP), AOPD, BNS,
protective guards, two- hand-
operating panels…
Actuator level: Relays, contactors, signal/indicator lamps...
Summary of Contents for PROTECT-PSC
Page 4: ......
Page 8: ......
Page 112: ......
Page 132: ......
Page 252: ......
Page 265: ...Annex 8 Instruction Manual PROTECT PSC V 2 6R01 04 19 8 5 8 3 EC Type Examination certificate ...
Page 266: ...Annex 8 Instruction Manual PROTECT PSC V 2 6R01 04 19 8 6 8 4 Declarations of conformity W ...
Page 267: ...Annex 8 Instruction Manual PROTECT PSC V 2 6R01 04 19 8 7 8 5 Index ...