3

PROTECT SRB 101EXi-1R

Operating instructions
Safety-monitoring module

EN

Utilisation category to IEC/EN 60947-5-1:

 

AC-15: 230 V / 3 A  

DC-13: 24 V / 3 A

Dimensions H x W x D:

 

100 mm x 22,5 mm x 121 mm

The data specified in this manual is applicable when the component is 
operated with rated operating voltage U

e

 ± 0%

.

EX-relevant Data 

EC-prototype test certificate: 

TÜV 08 ATEX 7522

- Designation:

 

L

 II (2) G [Ex ib Gb] IIC  

L

 II (2) D [Ex ib Db] IIIC  

(Circuit in Zone 1, 21 / 2, 22)

EC-prototype test certificate: 

TÜV 08 ATEX 7557 X

- Designation:

 

L

 II 3 G Ex nA nC IIC T5 Gc  

(SRB in Zone 2)

IECEx:

 

IECEx TUR 15.0xxxx

- Designation:

 

[Ex ib Gb] IIC  

[Ex ib Db] IIIC  

Ex nA nC IIC T5 Gc

INMETRO:

 

DNV 14.0041

- Designation:

 

[Ex ib Gb] IIB  

[Ex ib Gb] IIC  

[Ex ib Db] IIIC

Maximum safety voltage U

m

:

 

253 VAC  

 

(caution: Um is not a rated voltage!)

Inputs:

 

S11-S12, S21-S22, X1-X3: 

[Ex ib Gb] IIC bzw. [Ex ib Db] IIIC

Temperature class:  

T5

Voltage U

o

:

 

33,6 V

Current I

o

:

 

57,0 mA

Capacity P

o

:

 

478,8 mW (linear characteristic)

Separation (intrinsically safe / other circuits):

 

safe separation 

according to  

IEC/EN 60079-11  

(ABTN NBR IEC 60079-11),  

Voltage peak value 375 V

Gas group

II C

II B

External capacity  
Co (nF)

26

36

46

49 160 180 230 280 350 412

external inductivity 
Lo (mH)

4.0 2.0 1.0 0.5 38.0 5.0 2.0 1.0 0.5 0.2

Reference values for cable to EN 60079-14  
(cable with 2 or 3 conductors):

C ≈ 200 nF/km, L ≈ 1 mH/km (C ≈ 200 pF/m, L ≈ 1 µH/m)

Reference values for cable with 3 to 6 conductors:

C ≈ 400 nF/km, L ≈ 2 mH/km (C ≈ 400 pF/m, L ≈ 2 µH/m)

2.5  Safety classification

Standards: 

EN ISO 13849-1, IEC 61508

PL: 

up to e

Control category: 

up to 4

DC:

 

99% (high)

CCF:

 

> 65 points

PFH value: 

≤ 2.00 x 10

-8

/h

SIL: 

up to 3

Service life: 

20 years

The PFH values of 2.00 x 10

-8

/h apply to the combinations of contact 

load (current through enabling contacts) and number of switching cyc-
les (n

op/y

) mentioned in the table below. At 365 operating days per year 

and a 24-hours operation, this results in the below-mentioned switching 
cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 
and push up until it latches in position.

3.2  Mounting of the sensors

The installation of the intrinsically safe current circuits must be executed 
in accordance with the applicable standards IEC/EN 60079-14 (ABTN 
NBR IEC 60079-14.

According to IEC/EN 60079-11 (ABTN NBR IEC 60079-11), 
the following must be observed for the installation: a distance 

of ≥ 6 mm must be observed between the terminals of the 

intrinsically safe current circuits and other intrinsically safe 
current circuits. Between the terminals of the intrinsically 
safe current circuits and other, non-intrinsically safe current 

circuits, a distance of ≥ 50 mm must be observed.

The commissioning and installation are to be executed by 
qualified professionals only.

3.3  Installation in Zone 2: particular conditions

The devices must be installed in control or junction boxes, which meet 
the requirements to IEC/EN 60079-15 (ABTN NBR IEC 60079-15) and 
have at least protection class IP54 (Fig. 1). To respect temperature 
class T5, the device must have a free volume of at least 2,400 cm³.
Please make sure that you have read and understood these operating 
instructions and that you know all applicable legislations regarding 
occupational safety and accident prevention prior to installation and 
putting the component into operation.
The intrinsically safe current circuits of the device (light blue terminals) 
may be lead in explosion-endangered areas. In this case, it must be 
especially observed that they are safely separated from all non-intrinsi-
cally safe current circuits.

The connection and separation of the connections of  
non-intrinsically safe current circuits is not authorised  
in explosion-endangered atmospheres.
Only use a damp cloth to clean the enclosure.
The lifetime of the safety-monitoring related to  
the ignition protection class "nC" is at least 15 years.

Upon expiration of this time, the safety-monitoring modu-
le must be replaced either returned to the manufacturer 
for check-up!

The temperature specifications (–25 °C ≤ Ta ≤ +60 °C) of 

the safety-monitoring module are related to a volume of the 
control cabinet of at least approx. 2,400 cm³ for each SRB. 
The distance with regard to other safety-monitoring module 
imperatively must be at least approx. 5 cm.

Summary of Contents for PROTECT SRB 101EXi-1R

Page 1: ...lusively used in accordance with the versions listed below or for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter...

Page 2: ...y function is defined as the opening of release 13 14 when the inputs S11 S12 or S21 S22 are opened The safety relevant current path with output contact 13 14 meets the following requirements under ob...

Page 3: ...ions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Mounting of the sensors T...

Page 4: ...1 A2 is ON and the fuse F1 has not been triggered 5 2 Description of the terminals Voltages A1 24 VDC A2 0 VDC Inputs S11 S12 Input channel 1 S21 S22 Input channel 2 S21 S22 Input channel 2 with cross...

Page 5: ...d condition only Push up the bottom of the enclosure and hang out slightly tilted for wards 7 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with th...

Page 6: ...Fig 12 At least one contact with positive break required Wire breakage and earth leakage in the control circuits are detected Cross wire shorts between the control circuits are not detected For the sa...

Page 7: ...ding to IEC EN 60079 14 ABTN NBR IEC 60079 14 a declaration of the manufactu rer therefore can be used The devices classified as simple electrical apparatus can be used in the Zones 1 2 and 21 22 Only...

Page 8: ...lation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Notiied body T V Rheinland Industrie Service GmbH Am Grauen Stein 51105 K ln ID n 0035 Certiicate number 01 220 4316...

Reviews: