4

Operating instructions
Safety-monitoring module

PROTECT SRB 101EXi-1R

EN

5 cm

a)

b)

c)

d)

5 cm

5 cm

5 cm

Fig. 1
a)  IP54 control box suitable for installation in Zone 2 according to  

IEC/EN 60079-15 (ABTN NBR IEC 60079-15)

b)  Air around the safety-monitoring module approx. 2,400 cm³  

(8.25 × 16 × 18.1 cm)

c) Protection (suitable for Zone 2) 
d) Clips (suitable for Zone 2)

Potential equalisation: wiring of the PA terminals (Fig. 2)

The grounding of intrinsically safe circuits must be carried out in 
accordance with the requirements IEC/EN 60079-14 (ABTN NBR IEC 
60079-14).

U

EXi

U

B

U

i

K1
K2

SRB 
101EXi
-1R

0V X1 X2

S11 S12 S21 S22

13 14 21 22

PA PA A1 A2

2 x 1,5 mm

2

Fig. 2

3.4  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 
against unintentional contact of the connected and therefore 
electrically interconnected apparatus and the insulation of the 
feed cables must be designed for the highest voltage, which 
can occur in the device.

The electrical connection may only be carried out by autho-
rised personnel in a de-energised condition.

To avoid EMC disturbances, the physical ambient and opera-
tional conditions at the place where the product is installed, 
must meet the provisions laid down in the paragraph "Electro-
magnetic Compatibility (EMC)" of DIN EN 60204-1.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

• K1: Status channel 1

• K2: Status channel 2

• U

B

:  Status operating voltage (LED is on, when the  

operating voltage on the terminals A1-A2 is ON)

•  U

i

: Status internal operating voltage (LED is on, when the  

operating voltage on the terminals A1-A2 is ON and the fuse has not 
been triggered).

• UEXi:  Status internal operating voltage (LED is on, when the 

 

operating voltage on the terminals A1-A2 is ON and the fuse F1 
has not been triggered)

5.2  Description of the terminals

Voltages:

A1

+24 VDC

A2

0 VDC

Inputs:

S11-S12

Input channel 1 (+)

S21-S22

Input channel 2 (+)

S21-S22

Input channel 2 (–) (with cross-wire short 

detection)

Outputs:

13-14

Safety release

21-22

Auxiliary NC contact as signalling contact

Start:

X1-X2

Feedback circuit and external reset

Signalling outputs must not be used in safety circuits.

5.3  Operating principle

•  The SRB 101EXi-1R is a dual-channel safety-monitoring module for 

monitoring emergency stop command devices, guard door monitors 
and magnetic safety switches.

•  When the safety circuits S11-S12 and S21-S22 and the feedback 

circuit X1-X3 is closed, the safety-monitoring module is started and 
the enabling circuit 13-14 is closed.

•  The enabling circuit 13-14 is immediately opened when the emergen

-

cy stop command device or another safety equipment is operated.

•  Through the signalling path 21-22 an external control of the switching 

condition of the SRB 101EXi-1A can be signalled for instance.

•  The safety-monitoring module can only be restarted, when both chan

-

nels K1 and K2 have been enabled.

5.4  Adjustment
Opening the front cover (see Fig. 3)

•  To open the front cover, insert a slotted screwdriver in the top and 

bottom cover notch and gently lift it.

•  When the front cover is open, the electrostatic discharge requirements 

must be respected and observed.

•  After setting, the front cover must be fitted back in position.

Setting the switch (see Fig. 4)

•  The cross-wire short monitoring function (factory setting) is program

-

med by means of the switch underneath the front cover of the safety-
monitoring module.

•  The switch must only be operated in de-energised condition by means 

of a finger or an insulated blunt tool.

•  Pos. nQS (top): Not cross-wire short proof, suitable for 1-channel 

applications with outputs connected to potential in the control circuits.

•  Pos. QS (bottom), Cross-wire short proof: suitable for 2-channel appli

-

cations without outputs connected to potential in the control circuit s.

Only touch the components after electrical discharge!

Summary of Contents for PROTECT SRB 101EXi-1R

Page 1: ...lusively used in accordance with the versions listed below or for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter...

Page 2: ...y function is defined as the opening of release 13 14 when the inputs S11 S12 or S21 S22 are opened The safety relevant current path with output contact 13 14 meets the following requirements under ob...

Page 3: ...ions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Mounting of the sensors T...

Page 4: ...1 A2 is ON and the fuse F1 has not been triggered 5 2 Description of the terminals Voltages A1 24 VDC A2 0 VDC Inputs S11 S12 Input channel 1 S21 S22 Input channel 2 S21 S22 Input channel 2 with cross...

Page 5: ...d condition only Push up the bottom of the enclosure and hang out slightly tilted for wards 7 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with th...

Page 6: ...Fig 12 At least one contact with positive break required Wire breakage and earth leakage in the control circuits are detected Cross wire shorts between the control circuits are not detected For the sa...

Page 7: ...ding to IEC EN 60079 14 ABTN NBR IEC 60079 14 a declaration of the manufactu rer therefore can be used The devices classified as simple electrical apparatus can be used in the Zones 1 2 and 21 22 Only...

Page 8: ...lation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Notiied body T V Rheinland Industrie Service GmbH Am Grauen Stein 51105 K ln ID n 0035 Certiicate number 01 220 4316...