Operating instructions
Safety-monitoring module

PROTECT SRB 101EXi-1R

EN

8.3  Sensor configuration

Single-channel emergency stop circuit with command devices to 
DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 8)

•  Wire breakage and earth leakage in the control circuits are detected.

•  For the safety circuits monitoring, the emergency stop command 

 

devices may be designed as "simple electrical apparatus".

•  Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

•  Control category 1 – PL c to DIN EN ISO 13849-1 possible.

Dual-channel emergency stop circuit with command devices to 
DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 9)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  For the safety circuits monitoring, the emergency stop command 

 

devices may be designed as "simple electrical apparatus".

•  Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

•  Control category 4 – PL e to DIN EN ISO 13849-1 possible (with 

protective wiring).

Dual-channel emergency stop circuit with command devices to 
DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 10)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

•  For the safety circuits monitoring, the emergency stop command 

devices may be designed as "simple electrical apparatus".

•  Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

•  Control category 4 – PL e to DIN EN ISO 13849-1 possible.

S12

S11

S22

S12

nQS

QS

S12 S22

S21

S11

nQS

QS

S12

S11

S22

S21

nQS

QS

Fig. 8

Fig. 9

Fig. 10

Single-channel guard door monitoring circuit with interlocking 
devices to ISO 14119 (Fig. 11)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  For the safety circuits monitoring, the interlocking devices may be 

designed as "simple electrical apparatus".

• Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

• Control category 1 – PL c to DIN EN ISO 13849-1 possible.

Dual-channel guard door monitoring circuit with interlocking 
device to ISO 14119 (see Fig. 12)

•  At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

• Cross-wire shorts between the control circuits are not detected.

•  For the safety circuits monitoring, the interlocking devices may be 

designed as "simple electrical apparatus".

• Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

•  Control category 4 – PL e to DIN EN ISO 13849-1 possible (with 

protective wiring).

Dual-channel guard door monitoring circuit with interlocking 
device to ISO 14119 (Fig. 13)

• At least one contact with positive break required.

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

•  For the safety circuits monitoring, the interlocking devices may be 

designed as "simple electrical apparatus".

• Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

• Control category 4 – PL e to DIN EN ISO 13849-1 possible.

S12

S11

S22

S12

nQS

QS

S12

S11

S22

S21

nQS

QS

S12

S11

S22

S21

nQS

QS

Fig. 11

Fig. 12

Fig. 13

Dual-channel control of magnetic safety switches to EN 60947-5-3 
(see Fig. 14)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  For the safety circuits monitoring, the magnetic safety sensors may be 

designed as "simple electrical apparatus".

• Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

• Control category 3 – PL e to DIN EN ISO 13849-1 possible.

Dual-channel control of magnetic safety switches to EN 60947-5-3 
(see Fig. 15)

•  Wire breakage and earth leakage in the control circuits are detected.

• Cross-wire shorts between the control circuits are detected.

•  For the safety circuits monitoring, the magnetic safety sensors may be 

designed as "simple electrical apparatus".

• Examples see chapter 9 Simple "electrical apparatus – intrinsic safety"

• Control category 4 – PL e to DIN EN ISO 13849-1 possible.

The connection of magnetic safety switches to the SRB 
101EXi-1R  
safety-monitoring module is only admitted when the require-
ments of  
the standard EN 60947-5-3 are observed.

As the technical data are regarded, the following minimum 
requirements must be met:
– switching capacity: min. 500 mW
– switching voltage: min. 33.6 VDC
– switching current: min. 57 mA

S12

S11

S22

S21

nQS

QS

S12

S11

S22

S21

nQS

QS

Fig. 14

Fig. 15

Summary of Contents for PROTECT SRB 101EXi-1R

Page 1: ...lusively used in accordance with the versions listed below or for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter...

Page 2: ...y function is defined as the opening of release 13 14 when the inputs S11 S12 or S21 S22 are opened The safety relevant current path with output contact 13 14 meets the following requirements under ob...

Page 3: ...ions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Mounting of the sensors T...

Page 4: ...1 A2 is ON and the fuse F1 has not been triggered 5 2 Description of the terminals Voltages A1 24 VDC A2 0 VDC Inputs S11 S12 Input channel 1 S21 S22 Input channel 2 S21 S22 Input channel 2 with cross...

Page 5: ...d condition only Push up the bottom of the enclosure and hang out slightly tilted for wards 7 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with th...

Page 6: ...Fig 12 At least one contact with positive break required Wire breakage and earth leakage in the control circuits are detected Cross wire shorts between the control circuits are not detected For the sa...

Page 7: ...ding to IEC EN 60079 14 ABTN NBR IEC 60079 14 a declaration of the manufactu rer therefore can be used The devices classified as simple electrical apparatus can be used in the Zones 1 2 and 21 22 Only...

Page 8: ...lation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Notiied body T V Rheinland Industrie Service GmbH Am Grauen Stein 51105 K ln ID n 0035 Certiicate number 01 220 4316...