Installation manual
Page 112 of204
Function
Designation Response
time [ms]
Explanation
Activation / deactivation digital
output in extension module via
PAA in basic module
T
OUT_31
8
Activation or deactivation of an
output in the extension module
PSCBR-E-31-12DI-10DIO after
changes to the PAA in the basic
module.
Determination of the total response time
T
TOTAL
= T
IN
+ T
PLC
+ T
OUT
Example 1:
Input to extension module, activation of SLS and processing in PLC, output to basic module.
T
TOTAL
= T
IN_31
+ T
PLC
+ T
OUT_Base
= 18 ms + 8 ms + 0 ms = 24 ms;
Example 2:
Input to basic module, activation of SLS and processing in PLC, output to extension module.
T
TOTAL
= T
IN_Base
+ T
PLC
+ T
OUT_31
= 10 ms + 8 ms + 8 ms = 26 ms;
Example 3:
Input to extension module, activation of SLS and processing in PLC, output to extension module.
T
TOTAL
= T
IN_31
+ T
PLC
+ T
OUT_31
= 18 ms + 8 ms + 8 ms = 34 ms;