Installation manual
Page 115 of204
7.3.2 Reset-Timing
The reset-input for a internal reset is time monitored in „RUN“-mode. A internal reset is called by
a falling edge of the reset-input under the pre-condition of T<3sec between raising / falling edge.
Reset_In
Reset_Status
Max. 3 sec
Max. 3 sec
Max. 3 sec
7.3.3 Reset-Function
Function block
General
Reset
Internal
Reset
Function
Fatal Error
X
Failure reset
Alarm
X
X
Alarm reset
Safe monitore function
X
X
Reset of triggered safe monitoring functions
Flip-Flop
X
X
Dominant reset for 1 cycle
Timer
X
X
Timer = 0
After a reset the status of the safe monitoring functions is rebuild
If process values are beyond the parameterized trigger points, the status of the safe
monitoring functions is kept unchanged.
On time based functions, the timer value is reset and therefore the output status of the
relates function too. The function is triggered again if the time value versus monitored
status exceeds again the parameterized limits.
Pos_Ist
Reset_In
SOS_Result
SOS_Pos_Max
SOS_Pos_Min
Max. 3 sec
Max. 3 sec
Pos_Ist > SOS_Pos_Max
Example 1 for process value based safe monitoring function (SOS with position monitoring) =>
no change in output status after reset if position is out of the parameterized limits.