Installation manual
Page 12 of204
Digital I/O extension for PSCBR-C-10/11/12 series.
The extension module has 12 safe inputs, 10 safe I/O for optional configuration as input or
output and 2 signal outputs.
Communication modules
Extension module for the transfer of diagnostic and status data to an imposed control by
means of standard field bus.
3.1 Characteristic data of device
3.1.1 Basic modules
3.1.1.1 PSCBR-C-10
Type designation
Device design
Design of module with the following periphery:
14
digital inputs
2
pulse outputs
2
relay outputs
2
LOSIDE
2
HISIDE
2
signal outputs
1
diagnostic and configuration interface
1
function button
1
7-segment display
1
status LED
14
status LEDs for inputs
2
status LEDs for pulse outputs
2
status LEDs for relay outputs
2
status LEDs for HISIDE
1
backplane bus interface
Characteristics of the module:
Logic processing up to Pl e acc. to EN ISO 13849-1 or SIL 3 acc. to EN 61508
Freely programmable small control system for up to 800 IL instructions
Logic diagram oriented programming
Pulse outputs for cross-shorting detection of digital input signals
Safety function of external contact monitoring for connected switchgear
Monitored relay outputs for safety relevant functions
Monitored HISIDE/LOSIDE outputs for safety relevant functions
CAN-communication in connection with the PSCBR-F for diagnose via backplane bus
system mounted on top-hat rail.
Summary of Contents for PSCBR-C-10 Series
Page 1: ...Installation manual Page 1 of204 Installation Manual For PSCBR modules Series PSCBR C 10...
Page 178: ...Installation manual Page 178 of 204...
Page 181: ...Installation manual Page 181 of 204 Example for a risk analysis Gefahrenanalyse Risk analysis...